Page 34
Owner’s Manual - SRF40
ENGLISH
7.5.1 Accessing the Control Module
Always turn off gas and electrical supply to the fireplace before servicing the controls.
1. Remove the barrier screen and glass door assemblies, and set them aside in a safe location.
2. It is not necessary to remove decorative glass media from the burner cover or accent glass panels
to gain access to the control module.
3. The control module is in the lower
front corner of the fireplace bottom. It
is secured to the fireplace with Velcro.
The gas control and variable halogen
lighting wiring is routed through the
lower right side opening to the gas
valve and variable halogen lighting wire
connections in the firebox. The 120V
power cord is routed through the lower
right side opening and plugged into the
Junction Box receptacle.
DETAIL P
7.6 Maintenance Frequency
Maintenance frequency must be determined individually for each application.
Some considerations are:
• Exposure to water, dirt, chemicals and heat can damage the gas control and shut down the control
system.
• Cycling frequency. Fireplaces that may cycle 50 times daily or more should be checked monthly.
• Intermittent use. Fireplaces that are used seasonally should be checked before shutdown and again
before the next use.
• Dusty, wet or corrosive environment. Because these environments can cause the gas control to
deteriorate more rapidly, the system should be checked more often.
• Any control should be replaced if it does not perform properly on checkout or service. In addition,
replace any module if it is wet or looks like it has been wet.