3.11 Configuring Relays
Figure 27 Relay Settings Page
1. Connect to the user interface as the
Admin
user. See
2. In the user interface, select
Settings > Relays
.
3. Each of the three relays is configured individually. For each relay:
a. Select relay
Mode
:
• In
Normal
mode, the relay is activated by the selected
Trigger
.
• In
Test
mode, the relay activation is controlled manually from the
Set test state
buttons.
If the relay is not used, select the
Test
mode. You can also use it to test that wiring has
been connected correctly.
b. Select relay
Trigger
:
•
Gas Caution
activates the relay if any gas level alert of
caution
severity is active.
•
Gas Alarm
activates the relay if any gas level alert of
alarm
severity is active.
•
Device Error
activates the relay if a device error is active.
Settings are applied immediately.
OPT100 User Guide
M211858EN-E
40