Response
40
hex
Value of first register (least significant word)
40
hex
00
hex
Value of second register (most significant word)
00
hex
0E
hex
Modbus RTU checksum
E8
hex
(silence for >3.5 bytes)
End of Modbus RTU frame
Communication Description
Register address
23 (1-based Modbus documentation format) =
0016
hex
(0-based format used in actual
communication).
Data format
Two 16-bit Modbus registers interpreted as IEEE
754 binary32 floating point value, least
significant word first.
Returned value
40400000
hex
, which is binary32 representation
of 3 (ppm).
Appendix A – Modbus Reference
69