2. Product overview
2.1 Introduction to MGP260 series
Vaisala CARBOCAP
â
MGP260 Series Multigas Probes for Methane, Carbon Dioxide, and
Humidity Measurement are compact and durable in situ probes for methane (CH
4
), carbon
dioxide (CO
2
), and humidity (H
2
O vapor) measurements in demanding biogas processing
conditions. MGP260 series probes are Ex certified for use in Ex Zone 0 (parts inserted into
process) and Ex Zone 1 (parts outside the process).
MGP260 probes can be installed directly into raw process gas, removing the need for sample
treatment. Application areas include anaerobic digestion of industrial and municipal waste and
sludge from waste water treatment, landfill gas monitoring, activated carbon filter monitoring
in biogas treatment process, and CHP engine feed gas monitoring.
The MGP260 series proprietary infrared technology provides superior stability and
repeatability. Thanks to condensation elimination through probe heating and corrosion-
resistant steel and plastic materials, the IP66-rated instruments are highly robust and durable.
MGP260 series measurement output options include 3 analog current output channels (4 … 20
mA) and Modbus RTU over RS-485. The probes also provide a 4 … 20 mA Ex ia input for
connecting an optional external pressure or temperature sensor.
For easy-to-use access to configuration, diagnostics, and calibration and adjustment
functionalities, MGP260 probes can be connected to Vaisala Insight PC software with a USB
cable accessory.
2.2 Basic features and options
• Available measurement parameters: methane (CH
4
), carbon dioxide (CO
2
), and humidity
(H
2
O vapor)
• Ex classification: IECEx and MET certified for use in Class I Division 2 and Zone 0/1
environments: for full Ex classifications, see
.
• Operating pressure: -500 ... +500 mbar
• 3 analog outputs (4 … 20 mA, scalable, isolated)
• Digital output: Modbus RTU over RS-485
• Optional external temperature or pressure sensor input (4 … 20 mA, Ex ia)
• Power supply input: 18 … 30 VDC
• Direct installation into process: for pipeline ports with 1.5" female NPT thread
• Compatible with Vaisala Insight PC software
2.2.1 Hazardous area safety
Do not install or use MGP260 in a hazardous area before reviewing
the safety information in
Using MGP260 series probes in hazardous locations
CAUTION!
Chapter 2 – Product overview
9
陕西威瑞仪器仪表有限公司 生产代理销售:实验检测设备 气象科学仪器设备
Tel:029-88186182 Web:www.xavery.cn Email:[email protected]
Summary of Contents for MGP260 Series
Page 8: ...MGP260 User Guide M212504EN A 6 Tel 029 88186182 Web www xavery cn Email sxvery 163 com...
Page 88: ...Tel 029 88186182 Web www xavery cn Email sxvery 163 com...
Page 90: ...Tel 029 88186182 Web www xavery cn Email sxvery 163 com...
Page 91: ...Tel 029 88186182 Web www xavery cn Email sxvery 163 com...
Page 92: ...www vaisala com Tel 029 88186182 Web www xavery cn Email sxvery 163 com...