Functional description

32

Installation instructions VRC 470 0020116690_00 

8

To activate this function, set an offset value (° K). The 
controller activates summer mode when the outside 
temperature is greater than or equal to the current tar-
get room tempe the set offset value. The target 
room temperature at night, for example, is the   set-back 
temperature. The controller deactivates summer mode 
when the outside temperature is less than the target 
room tempe the set offset value - 1 K.

8.4.12  

Setting the heating curve

Menu ¬ Installer level ¬ System configuration 
 [HEATING 1/2 ----] ¬ Heat curve

If the heating curve setting is not sufficient to control 
the living room climate according to the operator's 
wishes, you can adapt the heating curve setting made 
during installation.

8.4.13  

Setting the minimum flow temperature for 
 heating circuits

Menu ¬ Installer level ¬ System configuration 
 [HEATING 1/2 ----] ¬ Min. temperature

You can enter a minimum value for the flow temperature 
for each heating circuit, which should not be undershot 
during control. The controller compares the calculated 
flow temperature with the value set for the minimum 
temperature and, if there is a difference, adjusts to the 
higher value.

8.4.14  

Setting the maximum flow temperature for 
mixing circuit

Menu ¬ Installer level ¬ System configuration 
 [HEATING 2 ----] ¬ Max. temperature

Only with a connected VR 61/2
You can enter a maximum value for the flow tempera-
ture of HEATING 2, which should not be undershot dur-
ing control. The controller compares the calculated flow 
temperature with the value set for the maximum tem-
perature and, if there is a difference, adjusts to the 
lower value.

8.4.15  Reading the status of special operating modes

Menu ¬ Installer level ¬ System configuration 
 [HEATING 1/2 ----] ¬  Advanced functions

With this function, you can define if a special operating 
mode (advanced function), such as Party function, Inter-
mittent ventilation, etc. should be activated for a heating 
circuit. 

8.4.16  Specifying control modes outside time periods

Menu ¬ Installer level ¬ System configuration 
 [HEATING 1/2 ----] ¬ System off mode

This function enables you to specify, for each heating 
circuit separately, the controller functions in Automatic 
mode outside active time periods. 
Factory reset: Frost prot.
There are three control modes for selection, which 
you can adapt further by using the  Room temperature 
control:

 

Frost protection:

 The heating function is switched off 

and the frost protection function is active. The heat-
ing circuit pump is switched off.
If a second heating circuit is connected, the heating 
circuit pump is switched off and the heating circuit 
mixer is closed. The outside temperature is moni-
tored. When the outside temperature falls below 3 °C, 
the controller switches the heating pump on for 
10 minutes after the end of the  frost protection delay 
time. If a second heating circuit is connected, the 
heating circuit mixer remains closed. After the end of 
the time, the controller checks if the flow temperature 
is less than 13 °C. If the temperature is greater than 
13 °C, the heating circuit pump is switched off.
If a second heating circuit is connected, the tempera-
ture of the VF2 temperature sensor is evaluated and 
the heating circuit pump is switched off at a tempera-
ture greater than 13 °C. If the temperature is less than 
13 °C, the controller switches the heating function on 
and activates the heating circuit pump. The controller 
sets the target room temperature to 5 °C and checks 
again if the outside temperature has reached 4 °C. If 
the outside temperature is greater than 4 °C, it 
switches the heating function and the heating circuit 
pump off.

 

ECO:

 The heating function is switched off.

If a second heating circuit is connected, the heating 
circuit pump is switched off and the heating circuit 
mixer is closed. The outside temperature is moni-
tored. If the outside temperature falls below 3 °C, the 
controller switches the heating function on after the 
end of the frost protection delay time. The heating 
circuit pump is activated.
If a second heating circuit is connected, the heating 
circuit pump and the heating circuit mixer are acti-
vated. The controller controls the target room tem-
perature to the set "Night temperature". Despite the 
heating function being activated, the burner is only 
active on demand. The heating function remains 
active until the outside temperature rises above 4 °C, 
after which the controller switches the heating func-
tion off again, but the outside temperature monitor-
ing remains active.

 

–  

Night temperature:

 The heating function is switched 

on and the target room temperature is set to the set 
"Night temperature" and adjusted to the "Night tem-
perature".

Summary of Contents for VRC 470

Page 1: ...Installation instructions For the heating engineer GB IE Installation instructions VRC 470f...

Page 2: ...ng the hot water production status 28 8 2 4 Reading the collector temperature 28 8 2 5 Setting the frost protection delay 29 8 2 6 Setting the pump blocking time 29 8 2 7 Setting the maximum pre heati...

Page 3: ...r 35 8 6 11 Setting the flow volume of the solar circuit 35 8 6 12 Defining the setting for multi relay 35 8 6 13 Activating the solar pump kick 35 8 6 14 Setting the solar circuit protection 35 8 6 1...

Page 4: ...ore these so that they are available when required 1 3 Symbols used The symbols used in the text are explained below Sym bols for identifying dangers are also used in these oper ating instructions Sec...

Page 5: ...to the units and other property in the event of improper use or use for which they are not intended The Vaillant VRC 470 controller controls a heating sys tem in a weather compensated and time depende...

Page 6: ...s have been removed bridged or disabled Immediately rectify any faults and damage that may negatively affect safety Inform the operator that he must not cover the con troller with furniture curtains o...

Page 7: ...e temperature is low the controller increases the flow temperature and if the outside tem perature is high it reduces the flow temperature again Thus the controller absorbs fluctuations in the outside...

Page 8: ...470 1 2 3 4 5 Fig 3 3 Identification plate example Key 1 EAN code 2 Unit designation 3 Operating voltage 4 Current consumption 5 CE label 3 5 Accessories i If the controller is supplemented with acces...

Page 9: ...led in the boiler or if the second heating circuit is to be influenced decentrally you can use the remote control unit VR 81 2 You can use the remote control unit VR 81 2 to set the parameter Room tem...

Page 10: ...h or north west facing wall On building with up to three floors install the external sensor Section 4 5 at 2 3 of the total wall height and on buildings with more than three floors install it between...

Page 11: ...living room 3 4 4 7 6 5 3 2 1 3 Fig 4 2 Mounting the controller 1 Controller VRC 470 2 Wall mounting base 3 Mounting holes 4 Openings for cable entry 5 Pin header with terminals for the eBUS cable 6 W...

Page 12: ...ard to latch into the sides of the wall mounting base 4 5 Installing the external sensor b Caution Risk of material damage if fitted incor rectly Incorrect fitting can cause damage to the unit and the...

Page 13: ...ternal sensor Drill two holes with 6 mm diameter in accordance with the mounting holes 1 Insert the wall plugs supplied Fix the wall mounting base 4 to the wall with two screws The cable entry must po...

Page 14: ...ernal sensor VRC 693 1 Connection cable to the external sensor VRC 693 2 6 way edge connector for plug location X41 boiler Connect external sensor VRC 693 to the boiler as follows Connect the connecti...

Page 15: ...nd 4 is installed Disconnect the power supply to the boiler Secure the power supply to the boiler against being switched on again 1 2 Fig 5 3 Connecting the controller Key 1 VRC 470 2 Boiler terminal...

Page 16: ...t Step size select Factory reset Own setting min max Language Languages available for selection German Heating circuit 1 Generator circuit inactive Generator circuit Heating circuit 2 2 Zone mixing ci...

Page 17: ...nction The mode for hot water production is dependent on this and cannot be set separately Set the target room temperature Desired day tem perature Set the set back temperature Desired night temper at...

Page 18: ...evels the Operator level and the Installer level The reading and set up options in Operator level are also described in the operating instructions Below you can find the reading and set up options whi...

Page 19: ...Heating circuit conf Back 0 K List Ht crt 1 Heat Generator Heat Generator Status VF1 Back Off Off Off Domestic hot water Cyl temp current Cylinder charge pump Circulation pump Back 59 C Active Heat Ge...

Page 20: ...TD2 Back On 64 C 54 C Solar Status multi relay Solar pump runtime Reset solar runtime Back Change On 1963h 1963h No 130 C Solar Pump control Lead cylinder Solar flow voume Back Off 1 165l min LP ZP V...

Page 21: ...y 0 12 h 1 4 Pump Blocking Time Off 5 60 min 1 15 Max pre heat 0 300 min 10 0 Max pre switch off 0 120 min 10 0 OT constant heating Off 25 10 C 1 Off Raising temperature 2 0 15 K 0 Control modules Lis...

Page 22: ...t value C Flow temp current Current value C Pump status 2 Current value On Off Room temp control None Modulation Thermost None Summer mode offset 3 30 K 1 1 Heat curve 0 20 4 0 0 05 1 2 Min temperatur...

Page 23: ...osing Room temp control None Modulation Thermost None Summer mode offset 0 30 K 1 1 Heat curve 0 20 4 0 0 05 1 2 Min temperature 15 90 C 1 15 Max temperature 15 90 C 1 75 System off mode Eco Set back...

Page 24: ...ff Anti legionella time 0 00 23 50 hr min 10 min 4 00 Cylinder boost offset 3 15 40 K 1 25 Load pump 0 10 min 1 5 Paral cyl charge 2 Off On Off On Off LP ZP relay connection 2 no connect Circ pump Cha...

Page 25: ...linder 1 2 1 2 1 Solar flow volume 0 0 99 0 l min 0 5 3 5 Multi relay diff ctrl Cylinder2 diff ctrl Solar pump kick On Off On Off Off Solar circuit prot Off 110 150 C 1 130 Solar cylinder 1 1 Max temp...

Page 26: ...2 Actuator LP ZP HK1 P HK2 AUF HK2 ZU HK2 P Sensor VF2 VF2 VR 68 1 Actuator MA KOL1 P LEG P Sensor KOL1 SP1 SP2 Yield TD1 TD2 actoSTOR 4 Actuator ZP P1 P2 AL Sensor T1 T2 T3 T4 Anode 1 Appears only if...

Page 27: ...urr value 45 C Change code New code 000 999 1 000 1 Appears only if solar module VR 68 2 is connected 2 Appears only if mixing module VR 61 2 is connected 3 Appears only if mixing module VR 61 2 or so...

Page 28: ...an save a date day month year for the next regular service When the date for the next service appointment is reached the message Service is displayed in the basic display of the controller If a servic...

Page 29: ...stem configuration System Max pre heat This function allows you to start the heating function for the heating circuits a set amount of time before the first period of the day so that the target room t...

Page 30: ...nction key Mode then the mode is only changed for HEATING 1 HEATING 2 continues to be operated in Automatic mode 8 3 System configuration Heat generator 8 3 1 Reading the status of the heat generator...

Page 31: ...er status This function allows you to read the current status opening closing stationary of the heating circuit mixer for HEATING 2 8 4 10 Activating room temperature control Menu Installer level Syst...

Page 32: ...actory reset Frost prot There are three control modes for selection which you can adapt further by using the Room temperature control Frost protection The heating function is switched off and the fros...

Page 33: ...terminated automatically when the cylin der sensor SP1 measures a temperature of 60 C for more than 60 minutes or after a period of 120 minutes has elapsed to avoid getting stuck in this function if...

Page 34: ...he desired actuation of a cylinder charge pump LP or circulation pump ZP for an implemented hydraulic scheme The setting Not connected means that the output on the VR 61 2 is not used 8 6 System confi...

Page 35: ...the cylinder with cylinder sensor SP1 2 Cylinder 2 is the cylinder with cylinder sensor TD1 This function is only effective if you set Cylinder 2 for the multi relay when making the setting Sec tion 8...

Page 36: ...KOL1 exceeds the set value the controller switches the solar pump on and the solar cylinder is charged The difference value can be defined separately for two connected solar cylinders i Does not apply...

Page 37: ...all the selected operating modes are interrupted The controller controls the flow temperature of the con trolled heating circuit according to a pre set program regardless of the outside temperature T...

Page 38: ...modes for heating hot water production and the circulation pump Change heating circuit names Restore factory settings Activate advanced functions Set desired temperature for HEATING 1 HEATING 2 Set d...

Page 39: ...a cold water mixing valve is integrated as protec tion against scalding To avoid malfunctions provide information on which rules the operator must observe Only operate the heating system if it is in p...

Page 40: ...e sensor defective Sensor T3 fault Fault in temperature sensor 3 Temperature sensor 3 Cable defective plug connection not correct temper ature sensor defective Sensor T4 fault Fault in temperature sen...

Page 41: ...ive Sensor T4 fault Fault in temperature sensor 4 Temperature sensor 4 Cable defective plug connection not correct temperature sensor defective Heat exchanger calcified Heat exchanger of the boiler is...

Page 42: ...cordance with Vaillant instructions The system owner will be granted a warranty in accordance with the Vaillant terms and conditions All requests for work dur ing the guarantee period must be made to...

Page 43: ...er is disconnected from the power source The rest of the procedure depends on where the control ler is installed For wall mounting Insert a screwdriver into the slot 7 on the wall mounting base 2 Sect...

Page 44: ...ble cross section mm2 0 75 1 5 Protection type IP 20 Protection class III Max permitted ambient temperature C 50 Height mm 115 Width mm 147 Depth mm 50 Tab 13 1 Technical specifications VRC 470 13 2 S...

Page 45: ...10 to 60 min depending on the outside temperature If the heating flow temperature is lower than 13 C the boiler is switched on The target room temperature is regulated at 5 C If the outside tempera t...

Page 46: ...n pump the time periods determine the operating times In automatic mode the system is controlled as per the specified values in the time periods Room temperature The room temperature is the temperatur...

Page 47: ...ontact details 28 Entering the service date 28 Error history 41 Error messages 40 External sensor 7 10 14 Connecting the VRC 693 14 Connecting the VRC 9535 14 Installing the external sensor 12 F Facto...

Page 48: ...32 46 Settings for the operator 17 Setting the heating curve 32 Setting the maximum pre heating time 29 Setting the maximum pre switch off time 29 Setting the raising temperature 30 Setting the solar...

Page 49: ......

Page 50: ......

Page 51: ......

Page 52: ...0020116690_00 GBIE 042011 Subject to change Manufacturer Supplier 2702416_rev0...

Reviews: