5 Hydraulics installation
26
Installation and maintenance instructions Hydraulic Station 0020291544_01
–
Minimum clearance: 200 mm
4.6
Wall-mounting the product
1
1.
Cut the enclosed adhesive strips for noise reduction
into two equally sized pieces (3 cm x 3 cm).
2.
Affix the adhesive strips to the product as shown in the
figure.
1
3.
Check the load-bearing capacity of the wall.
4.
Note the total weight of the product.
5.
Only use fixing material that is permitted for the wall.
6.
If required, ensure that mounting apparatus on-site has
sufficient load-bearing capacity.
7.
Suspend the product on the unit mounting bracket from
above using the hanging bracket.
4.7
Removing the front casing
A
B
▶
Reinstall the components in the reverse order.
5
Hydraulics installation
5.1
Carrying out the installation preparations
▶
Install the following components, preferably from the
manufacturer's accessories:
–
An expansion relief valve, a stopcock and a mano-
meter on the heating return
–
A domestic hot water safety assembly and a stopcock
on the cold water supply
–
A stopcock on the heating flow
▶
Check whether the volume of the installed expansion
vessel is sufficient for the heating system. If required, in-
stall an additional expansion vessel, connected as close
to the product as possible, in the heating return.
▶
Install the connection pipes such that they are free from
mechanical stress.
▶
If you are using metallic pipes to connect the pipe to the
outdoor unit, earth the pipes.
▶
Heat-insulate the pipes.
▶
Only solder connectors if the connectors are not yet
screwed to the service valves.
▶
Carefully flush the heating installation before connecting
the product.
▶
Check whether the expansion relief valve's drain pipe-
work opposite the outdoor air remains open, is installed
in a frost-free environment, always runs downwards and
visibly ends in an open drain.