aroTHERM plus with DHW Cylinder, Decoupler, 1 Radiator Zone
Setting
Value
Installation
Adapt. heat curve Deactivated
Hybrid manager
Bivalence pt
Heating bivalence point
-20°
DHW bivalence point: -20°
Alternative point Off
ESCO
Heating off
Back-up boiler Off
Basic system diagram configuration
Basic system diagram code
10
HP control module configuration
MO 2 Circulation
pump
Circuit 1
Circuit type
Heating
OT switch-off threshold 30
o
Heat curve
**Site specific
Min. target flow
temperature
15
o
Max. target flow
temperature
45
o
Set-back mode Normal
Room temp. mod. Expanded
Zone 1
Cylinder Yes
Zone assignment
Control
Domestic hot water
Cylinder Active
Anti-legio. day
**User
preference
Anti-legio. time
**User
preference
Cylinder charging offset
15 K
Cyl. charg. anti-cycl. time
5 min