background image

UK aroTHERM plus Schematics 

and Installation Guide 

Controls: sensoCOMFORT VRC 720, VR92, VR71

This guide booklet contains information to assist in the design, installation and commissioning of your heat 

pump system. This booklet should be used alongside all the relevant manuals for the equipment supplied.

Please read the contents very carefully for a successful installation.

Table of Contents

Heat Pump Pre-Installation Checklist ............................................................................................................ 2

Terms and Conditions for Vaillant Schematic Diagrams ............................................................................ 3

Schematic Diagrams / System Configuration Relevant Settings.............................................................. 4

Commissioning technical guide - for use with sensoCOMFORT VRC720 controller......................... 102

Schematics Legend............................................................................................................................................ 118

Summary of Contents for UK aroTHERM plus

Page 1: ...et should be used alongside all the relevant manuals for the equipment supplied Please read the contents very carefully for a successful installation Table of Contents Heat Pump Pre Installation Check...

Page 2: ...HW Cylinder with Adequate Coil Rating When non Vaillant heat pump DHW cylinders are used it is recommended using cylinders with coil rating of minimum 4kW per 1m2 Correctly sized heat emitters for MCS...

Page 3: ...he system all operating instructions must be followed In no circumstances shall Vaillant be liable to you or any other third parties for any loss or damage including without limitation damage for loss...

Page 4: ...RM plus with DHW Cylinder HEX Module Decoupler 1 Radiator Zone 1 Underfloor Heating Zone 3rd Party 27 3 HEX only aroTHERM plus with DHW Cylinder HEX Module 1 Radiator Zone 30 aroTHERM plus with DHW Cy...

Page 5: ...5 7 No modules aroTHERM plus with DHW Cylinder 1 Radiator Zone 78 aroTHERM plus with DHW Cylinder 1 Underfloor Heating Zone 3rd Party 81 aroTHERM plus with DHW Cylinder 2 Radiator Zones 84 aroTHERM pl...

Page 6: ...US BUS BUS BUS BUS BUS BUS BUS BUS BUS BUS 3 12p BUS BUS BUS 2 2 12m DCF AF 12 1 10i 8a 9j 9h 2 12b 3 9g B A BUS BUS BUS BUS BUS 8e 7 10e BUS BUS BUS BUS BUS BUS BUS BUS BUS 2a 230 V 3 UV1 9r 9r 7 16...

Page 7: ...N L3 L2 L1 0 24 V 230 V Heat Pump 2a 230 V DHW HTG 230 V 0 24 V EVU 2 1 VF1 SP1 2 1 ME 2 1 DCF AF AF IO DCF BUS 2 1 N 1 2 ZH N UV1 Auf Zu MA2 N L MA1 N L 230V N L 230V N L EVU ME DCF AF SP1 VF1 BUS Z...

Page 8: ...tion Basic system diagram code 10 HP control module configuration MO 2 Circulation pump Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site specific Min target flow temperature...

Page 9: ...3 MA1 2 12m DCF AF EVU 2 UFHX DEMAND UFH WIRING CENTRE 1 UFHX FLOW UFHX RETURN 12s 5 10i 8a 9j 9h 2 12b 3 9g B A BUS BUS BUS 8e 7 10e BUS BUS BUS BUS BUS BUS BUS BUS BUS 2a 230 V 3 UV1 9r 9r 7 16 230...

Page 10: ...X200 N L3 L2 L1 0 24 V 230 V Heat Pump 2a 230 V 12m DHW HTG 230 V 0 24 V EVU 2 1 VF1 SP1 2 1 ME 2 1 DCF AF AF IO DCF BUS 2 1 N 1 2 ZH N UV1 Auf Zu MA2 N L MA1 N L 230V N L 230V N L EVU ME DCF AF SP1 V...

Page 11: ...system diagram configuration Basic system diagram code 10 HP control module configuration MO 2 Circulation pump Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site specific Auto...

Page 12: ...BUS BUS 12e BUS 230 V 3 3 12p BUS 2 2 12m DCF AF 2 ZN 9b 3 S2 R1 12 1 1 10i 8a 9j 9h 2 12b 3 9g B A BUS BUS BUS BUS 8e 7 10e BUS BUS BUS BUS BUS BUS BUS BUS BUS 2a 230 V 3 UV1 9r 9r 7 16 230 V 3 17 1...

Page 13: ...1 2 S10 1 2 S11 1 2 S12 I 0 I _ 230 V 12e 12p 3 12 12a DHW CYL 3 12m 24V S21 24V S20 BUS X206 X200 N L3 L2 L1 0 24 V 230 V Heat Pump 2a 230 V DHW HTG 230 V 0 24 V EVU 2 1 VF1 SP1 2 1 ME 2 1 DCF AF AF...

Page 14: ...MO 2 Circ pump Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site specific Min target flow temp 15o Max target flow temp 45o Set back mode Normal Room temp mod Expanded Circui...

Page 15: ...BUS BUS BUS BUS BUS 12e BUS 230 V 3 3 12p BUS 2 2 12m DCF AF 10i 8a 9j 9h 2 12b 3 9g B A BUS BUS BUS BUS 8e 7 10e BUS BUS BUS BUS BUS BUS BUS BUS BUS 2a 230 V 3 UV1 9r 9r 7 16 230 V 3 17 11 HOT WATER...

Page 16: ...S8 1 2 S9 1 2 S10 1 2 S11 1 2 S12 I 0 I _ 230 V 12e 12p 3 12 DHW CYL 3 12m 24V S21 24V S20 BUS X206 X200 N L3 L2 L1 0 24 V 230 V Heat Pump 2a 230 V DHW HTG 230 V 0 24 V EVU 2 1 VF1 SP1 2 1 ME 2 1 DCF...

Page 17: ...dule configuration MO 2 Circ pump Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site specific Min target flow temp 15o Max target flow temp 45o Set back mode Normal Room temp m...

Page 18: ...S BUS BUS BUS BUS BUS BUS BUS BUS BUS BUS BUS 3 12p BUS 2 2 12m DCF AF 12 1 10i 10f 8a 8g 9j 9h 2 12b UV1 3 9g B A BUS BUS BUS BUS 7h 3 MA1 8g 9j 9h 7 10e 10e BUS BUS BUS BUS BUS BUS BUS 2a 230 V 3 9r...

Page 19: ...X200 N L3 L2 L1 0 24 V 230 V Heat Pump 2a 230 V 12p 12 3 230 V 0 24 V EVU 2 1 VF1 SP1 2 1 ME 2 1 DCF AF AF IO DCF BUS 2 1 N 1 2 ZH N UV1 Auf Zu MA2 N L MA1 N L 230V N L 230V N L EVU ME DCF AF SP1 VF1...

Page 20: ...em diagram configuration Basic system diagram code 10 HP control module configuration MO 2 Circ pump Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site specific Min target flow...

Page 21: ...U 2 UFHX DEMAND UFH WIRING CENTRE 1 UFHX FLOW UFHX RETURN 7f 9d 3f 10j 3 MA1 12s 5 10i 10f 8a 8g 9j 9h 2 12b UV1 3 9g B A BUS BUS BUS 7h 3 MA1 8g 9j 9h 7 10e 10e BUS BUS BUS BUS BUS BUS BUS 2a 230 V 3...

Page 22: ...L1 0 24 V 230 V Heat Pump 2a 230 V UFH X DEMAND 12s UFH 1 DEMAND 230 V 0 24 V EVU 2 1 VF1 SP1 2 1 ME 2 1 DCF AF AF IO DCF BUS 2 1 N 1 2 ZH N UV1 Auf Zu MA2 N L MA1 N L 230V N L 230V N L EVU ME DCF AF...

Page 23: ...ff Basic system diagram configuration Basic system diagram code 10 HP control module configuration MO 2 Circ pump Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site specific Mi...

Page 24: ...BUS 12e BUS 230 V 3 3 12p BUS 2 2 12m DCF AF 7f 2 S1 9d 3f 10j 2 ZN 9b 3 S2 R1 12 1 1 2 ZN 9b 3 S3 R2 12a 2 2 10i 10f 8a 8g 9j 9h 2 12b UV1 3 9g B A BUS BUS BUS BUS 7h 3 MA1 8g 9j 9h 7 10e 10e BUS BU...

Page 25: ...I 0 I _ BUS S7 1 2 S8 1 2 S9 1 2 S10 1 2 S11 1 2 S12 I 0 I _ 230 V 12e 12p 3 12 12a 24V S21 24V S20 BUS X206 X200 N L3 L2 L1 0 24 V 230 V Heat Pump 2a 230 V 230 V 0 24 V EVU 2 1 VF1 SP1 2 1 ME 2 1 DCF...

Page 26: ...tion MO 2 Circ pump Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site specific Min target flow temp 15o Max target flow temp 45o Set back mode Normal Room temp mod Expanded Ci...

Page 27: ...S BUS 12e BUS 230 V 3 3 12p BUS 2 2 12m DCF AF 2 ZN 9b 3 S2 R1 12 1 1 7f 9d 3f 10j 3 10i 10f 8a 8g 9j 9h 2 12b UV1 3 9g B A BUS BUS BUS BUS 7h 3 MA1 8g 9j 9h 7 10e 10e BUS BUS BUS BUS BUS BUS BUS 2a 2...

Page 28: ...1 N 1 2 ZH N UV1 Auf Zu MA2 N L MA1 N L 230V N L 230V N L EVU ME DCF AF SP1 VF1 BUS ZH UV1 MA2 MA1 230 V 230 V 230 V 12b Heatpump Interface SEC CIRC BUFFER PL 230 V SYS FLOW ZN1 RAD 230V N L R1 N L R...

Page 29: ...l module configuration MO 2 Circ pump Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site specific Min target flow temp 15o Max target flow temp 45o Set back mode Normal Room te...

Page 30: ...10f 8a 8g 9j 9h 2 12b 7h 3 MA1 UV1 3 9g B A BUS BUS BUS BUS BUS 8g 9j 9h 7 10e 10e BUS BUS BUS BUS BUS BUS BUS BUS BUS 2a 230 V 3 9r 9d 10j 9r 7 16 230 V 3 17 11 HOT WATER OUTLET 5 12K 12l 8e MAINS I...

Page 31: ...L1 0 24 V 230 V Heat Pump 2a 230 V 12p 12 3 DHW HTG 230 V 0 24 V EVU 2 1 VF1 SP1 2 1 ME 2 1 DCF AF AF IO DCF BUS 2 1 N 1 2 ZH N UV1 Auf Zu MA2 N L MA1 N L 230V N L 230V N L EVU ME DCF AF SP1 VF1 BUS...

Page 32: ...agram configuration Basic system diagram code 10 HP control module configuration MO 2 Circ pump Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site specific Min target flow temp...

Page 33: ...2 12b 7h 3 MA1 UV1 3 9g B A BUS BUS BUS BUS 8g 9j 9h 7 10e 10e BUS BUS BUS BUS BUS BUS BUS BUS BUS 2a 230 V 3 9r 9d 10j 9r 7 16 230 V 3 17 11 HOT WATER OUTLET 5 12K 12l 8e MAINS INLET 8c SEC CIRCULATI...

Page 34: ...p 2a 230 V UFH X DEMAND 12s UFH 1 DEMAND DHW CYL 12m DHW HTG 230 V 0 24 V EVU 2 1 VF1 SP1 2 1 ME 2 1 DCF AF AF IO DCF BUS 2 1 N 1 2 ZH N UV1 Auf Zu MA2 N L MA1 N L 230V N L 230V N L EVU ME DCF AF SP1...

Page 35: ...system diagram configuration Basic system diagram code 10 HP control module configuration MO 2 Circ pump Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site specific Min target...

Page 36: ...S 12e BUS 230 V 3 3 12p BUS 2 2 12m DCF AF 2 ZN 9b 3 S2 R1 12 1 1 2 ZN 9b 3 S3 R2 12a 2 2 10i 10f 8a 8g 9j 9h 2 12b 7h 3 MA1 UV1 3 9g B A BUS BUS BUS BUS 8g 9j 9h 7 10e 10e BUS BUS BUS BUS BUS BUS BUS...

Page 37: ...S8 1 2 S9 1 2 S10 1 2 S11 1 2 S12 I 0 I _ 230 V 12e 12p 3 12 12a HEX MODULE DHW CYL 3 12m 24V S21 24V S20 BUS X206 X200 N L3 L2 L1 0 24 V 230 V Heat Pump 2a 230 V DHW HTG 230 V 0 24 V EVU 2 1 VF1 SP1...

Page 38: ...MO 2 Circ pump Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site specific Min target flow temp 15o Max target flow temp 45o Set back mode Normal Room temp mod Expanded Circuit...

Page 39: ...BUS 12e BUS 230 V 3 3 12p BUS 2 2 12m DCF AF 2 ZN 9b 3 S2 R1 12 1 1 10i 10f 8a 8g 9j 9h 2 12b 7h 3 MA1 UV1 3 9g B A BUS BUS BUS BUS 8g 9j 9h 7 10e 10e BUS BUS BUS BUS BUS BUS BUS BUS BUS 2a 230 V 3 9...

Page 40: ...2 S5 1 2 S6 1 2 S13 I 0 I _ BUS S7 1 2 S8 1 2 S9 1 2 S10 1 2 S11 1 2 S12 I 0 I _ 230 V 12e 12p 3 12 24V S21 24V S20 BUS X206 X200 N L3 L2 L1 0 24 V 230 V Heat Pump 2a 230 V DHW HTG 230 V 0 24 V EVU 2...

Page 41: ...ule configuration MO 2 Circ pump Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site specific Min target flow temp 15o Max target flow temp 45o Set back mode Normal Room temp mo...

Page 42: ...e 3 BUS BUS BUS BUS BUS SUB BUS BUS BUS BUS BUS BUS BUS BUS BUS BUS BUS 3 12p BUS BUS 2 2 12m X41 12 1 9d 3f 10j 3 X16 7f 2 X41 10i 2 1 2a BUS BUS BUS BUS BUS 10e 230 V 3 9r 7 9r 7 16 230 V 3 17 11 HO...

Page 43: ...206 X200 N L3 L2 L1 0 24 V 230 V Heat Pump 2a 230 V 12p 12 3 0 24 V 230 V 24V S21 24V L S20 N BUS X11 X100 X41 0 b 0 b DCF RF AF FB L N X13 L S N X14 L N X16 Connect Via Chock Block X300 N L3 L2 L1 L1...

Page 44: ...deactiv Basic system diagram configuration Basic system diagram code 10 HP control module configuration MO 2 Circ pump Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site speci...

Page 45: ...Zone 3rd Party 2 12m X41 BUS BUS BUS S21 UFHX DEMAND UFH WIRING CENTRE 1 UFHX FLOW UFHX RETURN 5 12s 6 2 9d 3f 10j 3 X16 7f 2 X41 10i 2 1 2a BUS BUS BUS BUS BUS 10e 230 V 3 9r 7 9r 7 16 230 V 3 17 11...

Page 46: ...S21 24V S20 BUS X206 X200 N L3 L2 L1 0 24 V 230 V Heat Pump 2a 230 V 0 24 V 230 V 24V S21 24V L S20 N BUS X11 X100 X41 0 b 0 b DCF RF AF FB L N X13 L S N X14 L N X16 Connect Via Chock Block X300 N L3...

Page 47: ...er Off Basic system diagram configuration Basic system diagram code 10 HP control module configuration MO 2 Circ pump Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site specifi...

Page 48: ...S BUS BUS 2 2 12m X41 2 ZN 9b 3 S2 R1 12 1 1 2 ZN 9b 3 S3 R2 12a 2 2 9d 3f 10j 7f 2 S1 10i 2 1 2a BUS BUS BUS BUS BUS 10e 230 V 3 9r 7 9r 7 16 230 V 3 17 11 HOT WATER OUTLET 5 12K 12l 8e MAINS INLET 8...

Page 49: ...1 2 S6 1 2 S13 I 0 I _ BUS S7 1 2 S8 1 2 S9 1 2 S10 1 2 S11 1 2 S12 I 0 I _ 230 V 12e 12p 3 12 12a 24V S21 24V S20 BUS X206 X200 N L3 L2 L1 0 24 V 230 V Heat Pump 2a 230 V ZN1 RAD 0 24 V 230 V 24V S21...

Page 50: ...pump Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site specific Min target flow temp 15o Max target flow temp 45o Set back mode Normal Room temp mod Expanded Circuit 2 Circuit...

Page 51: ...R1 12 1 1 UFH WIRING CENTRE 2 9b 3 2 9d 3f 10j 7f 2 S1 10i 2 1 2a BUS BUS BUS BUS BUS 10e 230 V 3 9r 7 9r 7 16 230 V 3 17 11 HOT WATER OUTLET 5 12K 12l 8e MAINS INLET 8c SEC CIRCULATION 3e 3 10c 2 X2...

Page 52: ...S4 1 2 S5 1 2 S6 1 2 S13 I 0 I _ BUS S7 1 2 S8 1 2 S9 1 2 S10 1 2 S11 1 2 S12 I 0 I _ 230 V 12e 12p 3 12 24V S21 24V S20 BUS X206 X200 N L3 L2 L1 0 24 V 230 V Heat Pump 2a 230 V ZN1 RAD 0 24 V 230 V...

Page 53: ...ration MO 2 Circ pump Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site specific Min target flow temp 15o Max target flow temp 45o Set back mode Normal Room temp mod Expanded...

Page 54: ...BUS 3 12p BUS 2 2 12m X41 12 1 10i 2 1 10f 8g 9j 9h 10e 2a BUS BUS BUS BUS BUS 10e 230 V 3 7 9r 7h 3 X16 9r 7 16 230 V 3 17 11 HOT WATER OUTLET 5 12K 12l 8e MAINS INLET 8c SEC CIRCULATION 3e 3 10c 2 X...

Page 55: ...BUS X206 X200 N L3 L2 L1 0 24 V 230 V Heat Pump 2a 230 V 12p 12 3 0 24 V 230 V 24V S21 24V L S20 N BUS X11 X100 X41 0 b 0 b DCF RF AF FB L N X13 L S N X14 L N X16 Connect Via Chock Block X300 N L3 L2...

Page 56: ...ridge deactiv Basic system diagram configuration Basic system diagram code 10 HP control module configuration MO 2 Circ pump Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site...

Page 57: ...9d 3f 10j 3 X16 10i 2 1 10f 8g 9j 9h 10e 2a BUS BUS BUS BUS BUS 10e 230 V 3 7 9r 7h 3 X16 9r 7 16 230 V 3 17 11 HOT WATER OUTLET 5 12K 12l 8e MAINS INLET 8c SEC CIRCULATION 3e 3 10c 2 X22 X11 12 aroT...

Page 58: ...24V S21 24V S20 BUS X206 X200 N L3 L2 L1 0 24 V 230 V Heat Pump 2a 230 V 0 24 V 230 V 24V S21 24V L S20 N BUS X11 X100 X41 0 b 0 b DCF RF AF FB L N X13 L S N X14 L N X16 Connect Via Chock Block X300...

Page 59: ...boiler Off Basic system diagram configuration Basic system diagram code 10 HP control module configuration MO 2 Circ pump Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site sp...

Page 60: ...BUS BUS BUS BUS BUS BUS BUS BUS BUS BUS BUS BUS BUS BUS 12e BUS 230 V 3 3 12p BUS 2 2 12m X41 2 ZN 9b 3 S2 R1 12 1 1 2 ZN 9b 3 S3 R2 12a 2 2 9d 3f 10j 10i 2 1 10f 8g 9j 9h 10e 2a BUS BUS BUS BUS BUS 1...

Page 61: ...6 1 2 S13 I 0 I _ BUS S7 1 2 S8 1 2 S9 1 2 S10 1 2 S11 1 2 S12 I 0 I _ 230 V 12e 12p 3 12 12a 24V S21 24V S20 BUS X206 X200 N L3 L2 L1 0 24 V 230 V Heat Pump 2a 230 V 0 24 V 230 V 24V S21 24V L S20 N...

Page 62: ...Circ pump Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site specific Min target flow temp 15o Max target flow temp 45o Set back mode Normal Room temp mod Expanded Circuit 2 Ci...

Page 63: ...H WIRING CENTRE 2 ZN2 9b 3 9d 3f 10j 10i 2 1 10f 8g 9j 9h 10e 2a BUS BUS BUS BUS BUS 10e 230 V 3 7 9r 7h 3 X16 9r 7 16 230 V 3 17 11 HOT WATER OUTLET 5 12K 12l 8e MAINS INLET 8c SEC CIRCULATION 3e 3 1...

Page 64: ...S5 1 2 S6 1 2 S13 I 0 I _ BUS S7 1 2 S8 1 2 S9 1 2 S10 1 2 S11 1 2 S12 I 0 I _ 230 V 12e 12p 3 12 24V S21 24V S20 BUS X206 X200 N L3 L2 L1 0 24 V 230 V Heat Pump 2a 230 V 0 24 V 230 V 24V S21 24V L S2...

Page 65: ...onfiguration MO 2 Circ pump Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site specific Min target flow temp 15o Max target flow temp 45o Set back mode Normal Room temp mod Exp...

Page 66: ...S 2 2 12m X41 12 1 10i 2 1 10f 8g 9j 9h 10e 2a BUS BUS BUS BUS BUS 10e 230 V 3 7 9r 9d 10j 9r 7 16 230 V 3 17 7h 2 3 X41 MA1 11 HOT WATER OUTLET 5 12K 12l 8e MAINS INLET 8c SEC CIRCULATION 3e 3 10c 2...

Page 67: ...06 X200 N L3 L2 L1 0 24 V 230 V Heat Pump 2a 230 V 12p 12 3 0 24 V 230 V 24V S21 24V L S20 N BUS X11 X100 X41 0 b 0 b DCF RF AF FB L N X13 L S N X14 L N X16 Connect Via Chock Block X300 N L3 L2 L1 L1...

Page 68: ...deactiv Basic system diagram configuration Basic system diagram code 10 HP control module configuration MO 2 Circ pump Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site speci...

Page 69: ...6 2 10i 2 1 10f 8g 9j 9h 10e 2a BUS BUS BUS BUS BUS 10e 230 V 3 7 9r 9d 10j 9r 7 16 230 V 3 17 7h 2 3 X41 MA1 11 HOT WATER OUTLET 5 12K 12l 8e MAINS INLET 8c SEC CIRCULATION 3e 3 10c 2 X22 X11 12 aroT...

Page 70: ...S21 24V S20 BUS X206 X200 N L3 L2 L1 0 24 V 230 V Heat Pump 2a 230 V 0 24 V 230 V 24V S21 24V L S20 N BUS X11 X100 X41 0 b 0 b DCF RF AF FB L N X13 L S N X14 L N X16 Connect Via Chock Block X300 N L3...

Page 71: ...er Off Basic system diagram configuration Basic system diagram code 10 HP control module configuration MO 2 Circ pump Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site specifi...

Page 72: ...BUS BUS BUS BUS BUS BUS BUS BUS BUS BUS 12e BUS 230 V 3 3 12p BUS BUS BUS 2 2 12m X41 2 ZN 9b 3 S2 R1 12 1 1 2 ZN 9b 3 S3 R2 12a 2 2 10i 2 1 10f 8g 9j 9h 10e 2a BUS BUS BUS BUS BUS 10e 230 V 3 7 9r 9...

Page 73: ...S3 1 2 S4 1 2 S5 1 2 S6 1 2 S13 I 0 I _ BUS S7 1 2 S8 1 2 S9 1 2 S10 1 2 S11 1 2 S12 I 0 I _ 230 V 12e 12p 3 12 12a 24V S21 24V S20 BUS X206 X200 N L3 L2 L1 0 24 V 230 V Heat Pump 2a 230 V ZN1 RAD 0 2...

Page 74: ...pump Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site specific Min target flow temp 15o Max target flow temp 45o Set back mode Normal Room temp mod Expanded Circuit 2 Circuit...

Page 75: ...FH WIRING CENTRE 2 ZN2 9b 3 10i 2 1 10f 8g 9j 9h 10e 2a BUS BUS BUS BUS BUS 10e 230 V 3 7 9r 9d 10j 9r 7 16 230 V 3 17 7h 2 3 X41 X16 11 HOT WATER OUTLET 5 12K 12l 8e MAINS INLET 8c SEC CIRCULATION 3e...

Page 76: ...S2 1 2 S3 1 2 S4 1 2 S5 1 2 S6 1 2 S13 I 0 I _ BUS S7 1 2 S8 1 2 S9 1 2 S10 1 2 S11 1 2 S12 I 0 I _ 230 V 12e 12p 3 12 24V S21 24V S20 BUS X206 X200 N L3 L2 L1 0 24 V 230 V Heat Pump 2a 230 V ZN1 RAD...

Page 77: ...uration MO 2 Circ pump Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site specific Min target flow temp 15o Max target flow temp 45o Set back mode Normal Room temp mod Expanded...

Page 78: ...BUS BUS BUS BUS BUS BUS 3 12p BUS BUS BUS 2 2 12m DCF AF 12 1 10i 8a 9j 9h 2 12b 3 9g B A BUS BUS BUS BUS BUS 8e 7 10e BUS BUS BUS BUS BUS BUS BUS BUS BUS 2a 230 V 3 UV1 9r 9r 9d 7 16 230 V 3 17 11 HO...

Page 79: ...L2 L1 0 24 V 230 V Heat Pump 2a 230 V 12p 12 3 230 V 0 24 V EVU 2 1 VF1 SP1 2 1 ME 2 1 DCF AF AF IO DCF BUS 2 1 N 1 2 ZH N UV1 Auf Zu MA2 N L MA1 N L 230V N L 230V N L EVU ME DCF AF SP1 VF1 BUS ZH UV...

Page 80: ...configuration Basic system diagram code 8 HP control module configuration MO 2 Circ pump Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site specific Min target flow temp 15o M...

Page 81: ...EVU 2 UFHX DEMAND UFH WIRING CENTRE 1 UFHX FLOW UFHX RETURN 12s 5 10i 8a 9j 9h 2 12b 3 9g B A BUS BUS BUS BUS 8e 7 10e BUS BUS BUS BUS BUS BUS BUS BUS BUS 2a 230 V 3 UV1 9r 9r 9d 7 16 230 V 3 17 11 H...

Page 82: ...230 V Heat Pump 2a 230 V UFH X DEMAND 12s UFH 1 DEMAND 230 V 0 24 V EVU 2 1 VF1 SP1 2 1 ME 2 1 DCF AF AF IO DCF BUS 2 1 N 1 2 ZH N UV1 Auf Zu MA2 N L MA1 N L 230V N L 230V N L EVU ME DCF AF SP1 VF1 B...

Page 83: ...al On Basic system diagram configuration Basic system diagram code 10 HP control module configuration MO 2 Circ pump Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site specific...

Page 84: ...US BUS 12e BUS 230 V 3 3 12p BUS 2 2 12m DCF AF 2 ZN 9b 3 S2 R1 12 1 1 2 ZN 9b 3 S3 R2 12a 2 2 10i 8a 9j 9h 2 12b 3 9g B A BUS BUS BUS BUS 8e 7 10e BUS BUS BUS BUS BUS BUS BUS BUS BUS 2a 230 V 3 UV1 9...

Page 85: ...1 2 S13 I 0 I _ BUS S7 1 2 S8 1 2 S9 1 2 S10 1 2 S11 1 2 S12 I 0 I _ 230 V 12e 12p 3 12 12a 24V S21 24V S20 BUS X206 X200 N L3 L2 L1 0 24 V 230 V Heat Pump 2a 230 V 230 V 0 24 V EVU 2 1 VF1 SP1 2 1 M...

Page 86: ...irc pump Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site specific Min target flow temp 15o Max target flow temp 45o Set back mode Normal Room temp mod Expanded Circuit 2 Cir...

Page 87: ...BUS BUS 12e BUS 230 V 3 3 12p BUS 2 2 12m DCF AF 2 ZN 9b 3 S2 R1 12 1 1 10i 8a 9j 9h 2 12b 3 9g B A BUS BUS BUS BUS 8e 7 10e BUS BUS BUS BUS BUS BUS BUS BUS BUS 2a 230 V 3 UV1 9r 9r 9d 7 16 230 V 3 1...

Page 88: ...5 1 2 S6 1 2 S13 I 0 I _ BUS S7 1 2 S8 1 2 S9 1 2 S10 1 2 S11 1 2 S12 I 0 I _ 230 V 12e 12p 3 12 24V S21 24V S20 BUS X206 X200 N L3 L2 L1 0 24 V 230 V Heat Pump 2a 230 V 230 V 0 24 V EVU 2 1 VF1 SP1 2...

Page 89: ...ion MO 2 Circ pump Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site specific Min target flow temp 15o Max target flow temp 45o Set back mode Normal Room temp mod Expanded Cir...

Page 90: ...Zone 3 BUS BUS BUS BUS BUS BUS BUS BUS BUS BUS BUS BUS BUS BUS BUS BUS 3 12p BUS 2 2 12m X41 7f 2 X41 12 1 9d 3f 10j 3 X16 HOT WATER OUTLET 5e 8e MAINS INLET 8c 230 V 3 10i 2 2a 10e BUS BUS BUS BUS B...

Page 91: ...4V S21 24V S20 BUS X206 X200 N L3 L2 L1 0 24 V 230 V Heat Pump 2a 230 V 12p 12 3 0 24 V 230 V 24V S21 24V L S20 N BUS X11 X100 X41 DCF RF AF FB L N X13 L S N X14 L N X16 X300 N L3 L2 L1 L1 230 V X22 1...

Page 92: ...m configuration Basic system diagram code 10 HP control module configuration MO 2 Not connected Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site specific Min target flow temp...

Page 93: ...ng Zone 3rd Party 2 12m X41 7f 9d 3f 10j 3 X16 BUS BUS BUS 1 6 S21 2 UFHX DEMAND UFH WIRING CENTRE 1 UFHX FLOW UFHX RETURN 5 12s HOT WATER OUTLET 5e 8e MAINS INLET 8c 230 V 3 10i 2 2a 10e BUS BUS BUS...

Page 94: ...ND 12s UFH 1 DEMAND 24V S21 24V S20 BUS X206 X200 N L3 L2 L1 0 24 V 230 V Heat Pump 2a 230 V 0 24 V 230 V 24V S21 24V L S20 N BUS X11 X100 X41 DCF RF AF FB L N X13 L S N X14 L N X16 X300 N L3 L2 L1 L1...

Page 95: ...tem diagram configuration Basic system diagram code 10 HP control module configuration MO 2 Not connected Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site specific Min target...

Page 96: ...BUS BUS BUS BUS BUS BUS BUS BUS BUS BUS BUS BUS BUS 12e BUS 230 V 3 3 12p BUS 2 2 12m X41 7f 2 X41 9d 3f 10j 3 X16 HOT WATER OUTLET 5e 8e MAINS INLET 8c 230 V 3 2 ZN 9b 3 S2 R1 12 1 1 2 ZN 9b 3 S3 R2...

Page 97: ...24V S1 1 2 S2 1 2 S3 1 2 S4 1 2 S5 1 2 S6 1 2 S13 I 0 I _ BUS S7 1 2 S8 1 2 S9 1 2 S10 1 2 S11 1 2 S12 I 0 I _ 230 V 12e 12p 3 12 12a 24V S21 24V S20 BUS X206 X200 N L3 L2 L1 0 24 V 230 V Heat Pump 2...

Page 98: ...Not connected Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site specific Min target flow temp 15o Max target flow temp 45o Set back mode Normal Room temp mod Expanded Circuit...

Page 99: ...BUS BUS BUS BUS BUS BUS BUS BUS BUS BUS BUS BUS BUS BUS 12e BUS 230 V 3 3 12p BUS 2 2 12m X41 7f 2 X41 9d 3f 10j HOT WATER OUTLET 5e 8e MAINS INLET 8c 230 V 3 2 ZN 9b 3 S2 R1 12 1 1 UFH WIRING CENTRE...

Page 100: ...1 2 S4 1 2 S5 1 2 S6 1 2 S13 I 0 I _ BUS S7 1 2 S8 1 2 S9 1 2 S10 1 2 S11 1 2 S12 I 0 I _ 230 V 12e 12p 3 12 24V S21 24V S20 BUS X206 X200 N L3 L2 L1 0 24 V 230 V Heat Pump 2a 230 V ZN1 RAD 0 24 V 23...

Page 101: ...configuration MO 2 Not connected Circuit 1 Circuit type Heating OT switch off threshold 30o Heat curve Site specific Min target flow temp 15o Max target flow temp 45o Set back mode Normal Room temp mo...

Page 102: ...through the selection Press OK the selection button below the display on the right to move to the month selection then again to the year and once more to move to the next screen In the same manner as...

Page 103: ...t system configuration settings in accordance to the schematic drawing of the system installed Select the assignment for the multi function output terminal of the flexoTHERM Anything can be selected i...

Page 104: ...figuration settings in accordance to the schematic drawing of the system installed If applicable select the configuration number Refer to page 20 for relevant system configuration settings in accordan...

Page 105: ...ed settings Press the menu button Scroll down and select Installer level The default code is 000 Select System configuration For the relevant settings in the VRC700 controller refer to page 21 Care mu...

Page 106: ...emperature of the heat emitters in that zone Where a Vaillant controller is used to control each zone it is recommended to have the Adaptive heat curve setting set to Yes under the system configuratio...

Page 107: ...not applicable if using VWZ AI 6 MB2 Cooling technology No Unless system is designed for cooling and coding resistor has been fitted Compressor current limit 5 7KW unit 13 16A 10 12KW unit 20 25A You...

Page 108: ...the controller would need to moved closer to the receiver in the first instance and eliminate an external influences Check ebus connection and polarity to receiver and power to outdoor unit Controlle...

Page 109: ...ore clicking yes to this question sensoCOMFORT will now scan for all eBUS components connected to the system Read only Control refers to the sensoCOM FORT Remote control address 1 refers to the VR92 H...

Page 110: ...Vaillant solar system only shown if VR70 71 installed Select the number of heating circuits Heating circuits and zones If a VR70 is installed then the number and type of circuits need to be selected...

Page 111: ...71 not applicable if a VRS 570 has been used or none Vaillant solar system only shown if VR70 71 installed Select the number of heating circuits Heating circuits and zones If a VR70 is installed then...

Page 112: ...user Automatic cooling Deactivated Activated Deactivated Deactivated unless cooling possible for installation and coding resistor has been fitted If Parameter Yes has been selected cooling mode starts...

Page 113: ...e if the PV contact is closed Conf ext inputs Bridge deactivated Open deactivated Bridge closed deactivated Open when selecting bridge deactiv 3rd party input is open when calling for heat Other S ter...

Page 114: ...tion Usually not connected For aroTHERM SPLIT this relates to FB 0 connections on X41 on indoor unit For VWZ AI heat pump interface this relates to ME terminal Circuit 1 9 Parameter Select Display Fac...

Page 115: ...tion to the effects of the Active setting the thermostat function is activated Cooling possible No Yes No No unless cooling coding resistor has been fitted and installation designed for cooling Dew po...

Page 116: ...10k Only with domestic hot water control via VRC 720 Max cyl charging time Off 20 120 min 60 min See below table Cyl charg anti cycl time 0 120 min 60 min 5 mins Parallel cyl charging No Yes No No Dom...

Page 117: ...ct Press the button 7 times to Max remaining feed head press top right hand button to adjust Note You may need to adjust max remaining feed head and recheck the flow rate in test menu sensor actuator...

Page 118: ...Non return Valve 10e Y Strainer 10i Flexible Connection 10j Magnetic Filter 11 Immersion Heater 12 sensoCOMFORT 12a VR92 12b Heat Pump Interface 12e Wiring Centre VR 71 12K High Limit Cut Out 12l Cyli...

Page 119: ...119...

Page 120: ...query you can contact us by phone or email Phone 0344 693 3133 Email technical vaillant co uk Advance support line Phone 0330 678 0878 General enquiries If you are unsure of who you need to speak to o...