Instructions for installation and servicing ecoTEC
Second diagnostic level
• As described above in the first diagnostic level, scroll
through the diagnostic number
d.97
.
• Change the displayed value to
17
(password) and press
the “
i
” button.
You are now in the second diagnostic level where all
information from the first diagnostic level (see table 8.2)
and the second diagnostic level (see table 8.3) is dis-
played.
Display
Meaning
Display value/adjustable value
d.17
Heating flow/return regulation changeover
0 = flow, 1 = return (factory setting: 0)
d.18
Pump mode (return)
0 = return, 1 = nonstop, 2 = winter (factory setting: 0)
d.19
Only in ecoTEC plus:
Operating modes of the two-speed heating pump
0 = pre ignition speed 1, hot water or heating speed 2, overrun speed
1
1 = pre ignition speed 1, hot water speed 2, heating speed 1, overrun
speed 1
2 = like 1, but speed in heating mode dependent on heating part load
d. 0 (if d.0 is below 60% of full load, then pump speed 1, other-
wise speed 2)
3 = always speed 2
(factory setting: 2)
d.20
Maximum set value for target cylinder temperature
(system boilers only)
Setting range: 50 to 70 °C (factory setting: 65 °C)
d.27
Switching accessory relay 1 in the accessory module
1 = Circulation pump (default)
2 = Ext. pump
3 = Storage charging pump
4 = Flue gas flap/extractor hood
5 = External gas valve
6 = External error message
d.28
Switching accessory relay 2 in the accessory module
1 = Circulation pump
2 = Ext. pump (default)
3 = Storage charging pump
4 = Flue gas flap/extractor hood
5 = External gas valve
6 = External error message
d.50
Offset for minimum speed
in rpm/10, adjustment range: 0 to 300
d.51
Offset for maximum speed
in rpm/10, adjustment range: -99 to 0
d.58
From the third quarter of 2006:
Activation of solar reheating
Setting range: 0 to 3
0 = solar reheating disabled (factory setting)
3 = activation of min. hot water target value = 60 °C for solar
reheating
d.60
Number of safety temperature limiter cut offs
Quantity
d.61
Number of lock outs
Number of unsuccessful ignitions in the last attempt
d.64
Average ignition time
in seconds
d.65
Maximum ignition time
in seconds
d.68
Unsuccessful ignitions in the first attempt
Quantity
d.69
Unsuccessful ignitions in the second attempt
Quantity
d.70
Set diverter valve position
0 = Normal mode (factory setting)
1 = Centre position
2 = permanent heating position
d.71
Maximum setting of heater control knob
Adjustment range in °C: 40 to 85 (Factory setting: 75)
d.72
Pump overrun time after warm start (combination boil-
ers only) or charging an electronically controlled hot
water storage through C1-C2 (system boilers only)
Adjustment range in sec: 0, 10, 20 to 600
Factory setting for combination boilers: 80
Factory setting for system boilers: 300
d.73
Offset for warm start target value (combination boilers
only)
Adjustment range: -15 K to +5 K (Factory setting: 0 K)
d.75
Maximum charging time for a storage without own con-
troller (system boilers only)
Adjustment range in min: 20, 21, 22 to 90 (Factory setting: 45)
d.77
Storage partial load (storage charging capacity limit,
system boilers only)
Adjustment range in kW: appliance-specific
Factory setting: max. output
Table 8.3 Diagnostics codes of the second diagnostic level
Scrolling and changing values and exiting the diagnostic
mode is done as described in the first diagnostic level.
Note
After exiting the second diagnostic level, if you
press “i” and “+” within 4 minutes, you will
directly reach the second diagnostic level with-
out having to enter the password again.
Troubleshooting 8
Summary of Contents for ecoTEC plus 612
Page 54: ...Supplied By www heating spares co Tel 0161 620 6677...
Page 55: ...Supplied By www heating spares co Tel 0161 620 6677...
Page 56: ...Supplied By www heating spares co Tel 0161 620 6677 839592_05 GB 08 2006...
Page 122: ...Supplied By www heating spares co Tel 0161 620 6677...
Page 124: ...Supplied By www heating spares co Tel 0161 620 6677 0020010870 01 GB 03 2006 2...
Page 142: ...Supplied By www heating spares co Tel 0161 620 6677 0020010870 01 GB 03 2006 20...
Page 162: ...Supplied By www heating spares co Tel 0161 620 6677 Notes 0020010870 01 GB 03 2006 40...
Page 163: ...Supplied By www heating spares co Tel 0161 620 6677...
Page 179: ...Supplied By www heating spares co Tel 0161 620 6677 15 Instructions for use ecoTEC...
Page 180: ...Supplied By www heating spares co Tel 0161 620 6677 16 Instructions for use ecoTEC...
Page 181: ...Supplied By www heating spares co Tel 0161 620 6677 20 C 20 C 15 C 5 C bar bar VRT VRC i F P...
Page 182: ...Supplied By www heating spares co Tel 0161 620 6677...
Page 183: ...Supplied By www heating spares co Tel 0161 620 6677 19 Instructions for use ecoTEC...
Page 184: ...Supplied By www heating spares co Tel 0161 620 6677 838402_04 GB 08 2006...