Instructions for installation and servicing ecoTEC
Code
Meaning
Cause
F.25
Interruption in the compact thermal module cable har-
ness
Compact thermal module cable harness defective
F.27
Incorrect sensing of flame
Flame detector defective
F.28
Appliance does not start: Attempts to ignite during start
failed
Faults in the gas supply such as:
- Gas meter or gas pressure detector defective
- Air in gas
- Gas flow pressure too low
- Fire protection tap has disengaged
Faults in the gas valve, wrong gas setting, igniter (ignition trans-
former, ignition cable, ignition plug) defective, ionisation current
stopped (cable, electrode), faulty earthing in appliance, electronics
defective
F.29
Flame goes off during operation and subsequent ignition
attempts failed
Gas supply temporarily stopped, faulty earthing of appliance
F.32
Fan speed variation
Fan blocked, plug not inserted correctly on fan, hall sensor defec-
tive, fault in cable harness, electronics defective
F.49
eBUS undervoltage
Short circuit on eBUS, overload on eBUS or two power sources on
eBUS with different polarity
F.61
Gas–valve control defective
Short circuit/earth (ground) leak in cable harness to gas valves, gas
valve assembly defective (earth/ground leak from coils), electronic
control system defective
F.62
Gas valve shutoff delay
Gas valve leaking, electronics defective
F.63
EEPROM error
Electronics defective
F.64
Electronics/NTC fault
Short-circuit in flow or return NTC or electronics defective
F.65
Electronics temperature too high
Electronics too hot due to external effect, electronics defective
F.67
Flame detector input signal is outside the limits
(0 or 5 V)
Electronics defective
F.70
No valid DSN in display and/or mainboard
Spare part failure display and maiboard interchanged at same time
and device specific number not adjusted
F.71
Flow NTC reports constant value (stuck at)
Flow NTC is defective
F.72
Flow and/or return NTC fault
Flow and/or return NTC is defective (tolerances too big)
F.73
Water pressure sensor signal out of range (too low)
Cable to water pressure sensor is broken or has a short-circuit at
0 V or water pressure sensor defective
F.74
Water pressure sensor signal out of range (too high)
Cable to water pressure sensor has a short-circuit at 5 V / 24 V or
internal fault in water pressure sensor
F.75
No pressure rise was detected on turning on the pump
Water pressure sensor or/and pump defective
Air in the heating system, quick bleeder defective
Too little water in appliance; check adjustable by-pass; connect
external expension vessel to return
F.76
Overheating protection on primary heat exchanger trig-
gered
Cable or cable connection of fuse in the primary heat exchanger
defective, or primary heat exchanger defective
F.77
condensate pump or feedback of accessorie blocks heat-
ing
condensate pump defective or flume flap feedback triggered
F.78
wrong configuration with accessory
link box VR65 connected to combination boiler
con
no communication to mainboard
connection error display mainboard
Table 8.4 Error codes (continued)
Troubleshooting 8
Summary of Contents for ecoTEC plus 612
Page 54: ...Supplied By www heating spares co Tel 0161 620 6677...
Page 55: ...Supplied By www heating spares co Tel 0161 620 6677...
Page 56: ...Supplied By www heating spares co Tel 0161 620 6677 839592_05 GB 08 2006...
Page 122: ...Supplied By www heating spares co Tel 0161 620 6677...
Page 124: ...Supplied By www heating spares co Tel 0161 620 6677 0020010870 01 GB 03 2006 2...
Page 142: ...Supplied By www heating spares co Tel 0161 620 6677 0020010870 01 GB 03 2006 20...
Page 162: ...Supplied By www heating spares co Tel 0161 620 6677 Notes 0020010870 01 GB 03 2006 40...
Page 163: ...Supplied By www heating spares co Tel 0161 620 6677...
Page 179: ...Supplied By www heating spares co Tel 0161 620 6677 15 Instructions for use ecoTEC...
Page 180: ...Supplied By www heating spares co Tel 0161 620 6677 16 Instructions for use ecoTEC...
Page 181: ...Supplied By www heating spares co Tel 0161 620 6677 20 C 20 C 15 C 5 C bar bar VRT VRC i F P...
Page 182: ...Supplied By www heating spares co Tel 0161 620 6677...
Page 183: ...Supplied By www heating spares co Tel 0161 620 6677 19 Instructions for use ecoTEC...
Page 184: ...Supplied By www heating spares co Tel 0161 620 6677 838402_04 GB 08 2006...