background image

9 Handing the product over to the end user

24

Installation and maintenance instructions ecoTEC exclusive 0020186710_06

Minimum volume flow:

180 l/h

Specify a pressure level and confirm by pressing

.

Wait until the volume flow has been set.

9

Handing the product over to the end
user

When you have finished the installation, affix the en-
closed sticker (which requests that the user reads the
instructions) to the front of the product in the end user's
language.

Explain to the end user how the safety devices work and
where they are located.

Inform the end user how to handle the product.

In particular, draw attention to the safety warnings which
the end user must follow.

Inform the end user that they must have the product
maintained in accordance with the specified intervals.

Pass all of the instructions and documentation for the
product to the end user for safe-keeping.

Inform the end user about measures taken to ensure the
combustion air supply and flue system, and instruct the
end user that he must not make any changes.

If the product is equipped with a communication unit for
connecting to a broadband Internet connection, point
out to the end user that they can download an app from
Google Play™ or the App Store™ and use it for mobile
operation.

In this case, point out to the end user the product inform-
ation sticker with Data Matrix Code that is on the rear of
the front flap, as they will need this in order to use the
app.

10 Troubleshooting

10.1

Comfort protection mode for the heat cell

Conditions

: Neither

nor a fault code

F.xx

are shown in the display

Unusual operating noises are emitted from the heat cell in
the product.

Check whether

S.40

is displayed in

Live monitor

.

If

S.40

is displayed, the product is in a temporary test mode,

which it will exit again automatically.

Conditions

:

is displayed.

The

Live monitor

shows

S.40

and

D.118

is at 0. The heat

cell is in permanent comfort protection mode. This is not
caused by the all-gas sensor.

Decommission the product and check the entire air/flue
pipe.

Are there any blockages or leakages?

Eliminate the cause.

Are any components damaged?

Replace the defective components.

If the air/flue pipe is OK, restart the product.

Prepare the flue gas analyser for checking the recircula-
tion.

The measuring probes must be rinsed and must not
be contaminated by a previous measurement.

Check for recirculation at the air test point. The following
measured values are indicators of recirculation.

Oxygen value in the intake air: < 20 vol. %

Intake air CO value:

100 ppm

Recirculation is present.

Eliminate the deficiencies in the air/flue pipe.

No recirculation is present.

Ensure that there is a heat requirement. In the
Live Monitor, check whether the product has the
status

S.04

or

S.14

.

If the combustion values are not OK, carry out check
programmes

P.04

and

P.14

.

Conditions

:

and

F.55

are displayed

The

Live monitor

shows

S.40

and

D.118

1. The heat cell

is in permanent comfort protection mode.

Check and, if required, replace the all-gas sensor.

10.2

Checking service messages

To obtain further information, call up the

Live Monitor

.

(

Page 16)

Conditions

:

S.40

is displayed

The product is in Comfort protection mode. The product has
detected a temporary fault and continues to run with restric-
ted comfort. The product switches back to the normal operat-
ing mode.

To establish whether or not a component is defective,
read the fault memory. (

Page 25)

Note

If no fault message is present, the product will
automatically switch back to normal operating
mode after a certain time.

Conditions

:

S.86

or

S.87

is displayed

The product remains in comfort safety mode and does not
switch back to normal operating mode.

Check the component that is mentioned and, if required,
replace it.

To establish whether or not a component is defective,
read the fault memory (

Page 25).

appears if you have set a maintenance interval, for ex-

ample, and this has passed or a service message is issued.

Summary of Contents for ecoTEC exclusive VC 156/5-7 N-DE

Page 1: ...usive VC 156 5 7 N DE VC 216 5 7 N DE VC 246 5 7 N DE VC 276 5 7 N DE VC 326 5 7 N DE DK VC 216 5 7 N DE DE Publisher manufacturer Vaillant GmbH Berghauser Str 40 D 42859 Remscheid Tel 49 21 91 18 0 F...

Page 2: ...nd supplementary water 18 7 7 Preventing low water pressure 19 7 8 Filling the heating installation 19 7 9 Purging the heating installation 20 7 10 Filling the condensate siphon 20 7 11 Starting up th...

Page 3: ...rvance of accompanying operating installation and servicing instructions for the product and any other system compon ents installing and fitting the product in accord ance with the product and system...

Page 4: ...flue gas installation or in a heat generator flue gas may escape Never operate the heat generator as an open flued system under any circum stances Always operate the heat generator using a return chec...

Page 5: ...5 Risk of material damage caused by using an unsuitable tool Use the correct tool 1 3 16 Risk of material damage caused by frost Do not install the product in rooms prone to frost 1 3 17 Risk of corro...

Page 6: ...0017111 3 Product description 3 1 Product design The product does not require a minimum volume flow 3 4 8 14 15 11 12 18 17 16 20 19 5 6 9 10 7 1 2 13 1 Flue gas test point 2 Connection for the air fl...

Page 7: ...ted on the identification plate The declaration of conformity can be viewed at the manufac turer s site 3 4 DVGW mark The DVGW mark documents that the products comply with all of the requirements of t...

Page 8: ...dish condensate siphon connection 13 Flue pipe connection Consult the installation template that is supplied to find the dimension A The product s installation depth B can be found in the tech nical d...

Page 9: ...ty of the wall 2 Note the total weight of the product 3 Only use fixing material that is permitted for the wall 4 If required ensure that mounting apparatus on site has sufficient load bearing capacit...

Page 10: ...ator cock that is installed upstream of the product relieve the gas line pressure before you open this gas isolator cock Caution Risk of material damage caused by corro sion Due to non diffusion tight...

Page 11: ...other units Observe the applicable international national and local regulations for flue gas systems in particular for installa tions in living rooms Inform the operator how to correctly operate the...

Page 12: ...common flue gas pipe may exceed the static pressure in the common air pipe The common air flue gas installation must have the following properties The wind protection device for the air flue gas syste...

Page 13: ...ue pipe 1 You can find out which flue pipes may be used by con sulting the enclosed flue pipe installation manual Conditions Installation in damp rooms You must connect the product to a room sealed ai...

Page 14: ...ial damage caused by incor rect installation Mains voltage at incorrect terminals and plug terminals may destroy the electronics Do not connect any mains voltage to the eBUS terminals Only connect the...

Page 15: ...not already a bridge Conditions Connecting a low voltage control 24 V Remove the bridge and connect the control to the 24 V RT connection X100 or X106 Conditions Connecting a limit thermostat to unde...

Page 16: ...g The settings options for more complex systems can be found in the Diagnostics menu Menu Installer level Diagnostics menu Press to confirm the start of the installation assistant All heating and hot...

Page 17: ...ylinder and heating mode default set ting On Note Green iQ mode is a special operating mode that can be used to save energy If this mode is activated the product operates in the heat ing and cylinder...

Page 18: ...6 Checking and treating the heating water filling and supplementary water Caution Risk of material damage due to poor qual ity heating water Ensure that the heating water is of suffi cient quality Be...

Page 19: ...sure of between 0 1 MPa and 0 2 MPa 1 0 bar and 2 0 bar If the heating installation extends over several storeys higher filling pressures may be required to avoid air entering the heating installation...

Page 20: ...or the correct measurement of gas flow pressure and CO content Deleting existing calibration values Calibrating in maximum mode Calibrating in minimum mode Install the front casing Ensure that there i...

Page 21: ...the product Note Since the combustion can be continuously monitored by the product you do not need to check the combustion 2 Press and at the same time to activate the max imum output operation If S 8...

Page 22: ...and confirm by pressing TFlow tar get C Set maximum burner anti cycling time min 1 5 10 15 20 25 30 30 2 0 4 0 8 5 12 5 16 5 20 5 25 0 35 2 0 4 0 7 5 11 0 15 0 18 5 22 0 40 2 0 3 5 6 5 10 0 13 0 16 5...

Page 23: ...al volume flow 20 K marked 8 4 1 3 VC 246 5 7 276 5 7 pump characteristic 200 100 300 400 500 600 700 800 900 1000 1100 1300 1200 1400 0 0 50 100 150 200 250 300 350 400 450 B A A Constant pressure re...

Page 24: ...18 is at 0 The heat cell is in permanent comfort protection mode This is not caused by the all gas sensor Decommission the product and check the entire air flue pipe Are there any blockages or leakage...

Page 25: ...lace any of the product s water bearing components 6 Make sure that water does not drip on live components e g the electronics box 7 Use only new seals 10 6 1 Risk of poisoning caused by flue gases du...

Page 26: ...gas valve steps offset and con firm by pressing 12 Enter the offset value that you read off and confirm by pressing 13 Carry out initial start up Page 20 10 7 3 Replacing the fan 1 Remove the air inta...

Page 27: ...d correctly on the flow and return connections 16 Install the compact thermal module Page 30 17 Install the left hand side section 18 Fill Page 19 and purge Page 20 the product and if required the hea...

Page 28: ...starts Page 16 8 Make the system specific settings 10 7 8 Replacing the all gas sensor 3 2 1 1 Remove the air intake pipe see Removing the compact thermal module Page 29 2 Undo the screws 3 just enou...

Page 29: ...eplace the seal each time you open the burner flange Replace the self locking nuts on the burner flange each time you open the burner flange If the insulating mat on the burner flange or on the back w...

Page 30: ...nsulating mat 11 3 4 Installing the compact thermal module 1 3 2 4 5 7 6 1 Connect the compact thermal module 5 to the heat exchanger 4 2 Tighten the four nuts 1 in a cross wise pattern until the burn...

Page 31: ...age 27 4 Fill the heating installation Page 19 5 Purge the heating installation Page 20 11 7 Completing inspection and maintenance work Check the gas flow pressure Page 20 Check the CO content Page 21...

Page 32: ...tion Default setting Min Max Installer level Enter code 00 99 1 competent person code 17 Installer level Fault list F XX F XX Current value Installer level Test programs Check programs P 00 Purging Ye...

Page 33: ...egionella protection pump not active 10 Solar valve not active 2 Accessory relay 2 1 10 1 Circulation pump 2 External pump 3 Cylinder charging pump 4 Extractor hood 5 External solenoid valve 6 Externa...

Page 34: ...remote control not active 9 Legionella protection pump not active 10 Solar valve not active 2 Accessory relay 1 1 10 1 Circulation pump 2 External pump 3 Cylinder charging pump 4 Extractor hood 5 Exte...

Page 35: ...ow temperature target value or return target value Not ad justable D 006 Outlet temperature target value Current value C Target domestic hot water temper ature combination products only Not ad justabl...

Page 36: ...ex ternal control 3 Eco intermittently operating pump Internal pump is switched on every 25 minutes for 5 minutes once the overrun time has elapsed 3 D 020 Max DHW temperature target value 50 70 C Ma...

Page 37: ...m h Actual value Circulation water volume for flow sensor Not ad justable D 033 Fan speed target value Current value rpm Not ad justable D 034 Fan speed actual value Current value rpm Not ad justable...

Page 38: ...parallel operation 2 Permanent heating position 0 D 071 Max heating target flow temp 40 80 C Target value maximum heating flow temperature 1 75 D 072 Pump overrun after cylin der charging 0 10 min In...

Page 39: ...value actoSTOR module detection 0 Not connected 1 Connection error 2 Connection active Not ad justable D 093 Adjust Device Specific Number 0 999 VC 156 5 7 N DE 201 VC 216 5 7 N DE 202 VC 246 5 7 N D...

Page 40: ...Fan start up S 22 DHW mode Pump pre run DHW mode Pump pre run S 23 DHW mode Ignition DHW mode Ignition S 24 DHW mode Burner on DHW mode Burner on S 25 DHW mode Pump fan overrun DHW mode Pump fan over...

Page 41: ...lation volume self test Water circulation volume self test S 93 Flue gas measurement not possible Flue gas measurement not possible because not all measuring programs have yet run S 96 Return temperat...

Page 42: ...gas valve assembly fault on the gas valve assembly multiple plug on PCB incorrectly plugged in break in cable harness ignition sys tem ignition transformer ignition cable ignition plug ignition electr...

Page 43: ...tive F 68 Fault Flame signal unstable Air in gas gas flow pressure too low incorrect air ratio condensate route blocked ionisation flow interruption cable electrode flue gas recirculation condensate r...

Page 44: ...e change registered at the flow and or return temperature sensor is non existent or too small Insufficient water in product Flow or return temperature sensor not in correct position at pipe F 84 Fault...

Page 45: ...10 9 3 2 4 1 2 3 L N L N L N X16 L N 1 2 3 1 2 3 19 1 20 8 17 7 18 6 4 3 1 M C1 C2 16 4 3 17 5 7 8 5 4 2 1 Masse PWM Hallsignal 24V Burner Off BUS RT 24V X100 4 2 10 11 2 3 1 5 8 1 6 8 3 5 1 2 4 1 2 3...

Page 46: ...so pay particular attention to signs of corrosion soot and other defects X X 4 Check the gas flow pressure at maximum heat input If the gas flow pressure is not within the correct range carry out mai...

Page 47: ...te discharge pipe min 19 mm 19 mm 19 mm 19 mm 19 mm 19 mm Gas connection pressure G20 natural gas 2 0 kPa 20 0 mbar 2 0 kPa 20 0 mbar 2 0 kPa 20 0 mbar 2 0 kPa 20 0 mbar 2 0 kPa 20 0 mbar 2 0 kPa 20 0...

Page 48: ...exclusive l e Nominal heat output range P at 50 30 C 1 9 15 3 kW 1 9 21 6 kW 1 9 25 6 kW 3 4 26 7 kW 3 8 32 9 kW 1 9 21 6 kW Nominal heat output range P at 80 60 C 1 7 14 2 kW 1 7 20 0 kW 1 7 23 9 kW...

Page 49: ...ue 3 5 to 4 0 in 50 30 C heating mode 1 45 l h 2 04 l h 2 42 l h 2 52 l h 3 12 l h 2 04 l h Remaining feed head of pump at nominal circula tion water volume 0 020 MPa 0 200 bar 0 020 MPa 0 200 bar 0 0...

Page 50: ...7 Control connecting 15 Corrosion 5 Corrugated gas pipe 5 D Decommissioning 31 Decommissioning temporarily 31 Diagnostics codes calling up 22 Disposal packaging 31 Disposing of the packaging 31 Docume...

Page 51: ...Replacing the burner 25 Replacing all gas sensor 28 Replacing expansion vessel 27 Replacing fan 26 Replacing gas family coding resistor 15 Replacing gas valve 25 Replacing heat exchanger 26 Replacing...

Page 52: ...8 0 Telefax 021 91 18 2810 Auftragsannahme Vaillant Kundendienst 021 91 5767901 info vaillant de www vaillant de These instructions or parts thereof are protected by copyright and may be reproduced or...

Reviews: