Start-up 6
0020273765_00 atmoMAG Installation and maintenance instructions
11
5.6
Connecting the flue pipe
1
2
▶
Use a flue pipe with the diameter that is specified in the
technical data to connect the product to a flue system
that has a natural draught (chimney).
▶
Insert the flue pipe
(1)
into the flue pipe connection
(2)
on
the down-draught diverter.
6
Start-up
6.1
Carrying out the initial start-up
Initial start-up must be carried out by a customer service
technician or a qualified competent person.
▶
Remove the product casing (
→
Page 9).
▶
When starting up the unit, proceed in accordance with
the attached checklist.
Commissioning checklist (
→
Page 20)
6.2
Checking and, if required, setting the water
flow rate
1.
Measure the water flow rate and compare the value
with the value specified in the technical data.
–
At initial start-up
–
After replacing the micro switch
1
2.
If the measured value exceeds the value specified in
the technical data, set the flow rate at the micro switch
(1)
.
–
Clockwise rotation: Increase the starting flow rate
–
Anti-clockwise rotation: Decrease the starting flow
rate
6.3
Gas conversion
If the product is installed in a mobile home, it must
not
be
converted to a different gas type (using a conversion set)
other than the one specified on the data plate.
▶
Leave the product in the gas type setting that was set at
the factory.
6.4
Gas conversion
1.
Observe the applicable national regulations.
2.
To convert the gas, use only Vaillant conversion sets or
Vaillant spare parts.
3.
Follow the instructions contained in the documentation
that is supplied with the conversion sets or spare parts.
Conditions
: Installation in a mobile home
▶
You must
not
convert the product to a gas type other
than the one that is specified on the data plate.
▶
Leave the product in the gas type setting that was set at
the factory.
6.5
Checking that the flue gas sensor works
correctly
If the flue system is fully or partially blocked or the local air
pressure conditions restrict the smooth flue system, the flue
gas sensor registers an increase in temperature and inter-
rupts the gas supply.
Check that the flue gas sensor is working correctly, as de-
scribed below.