Appendix
0020271943_00 atmoMAG Installation and maintenance instructions
23
Burner pressure
Gas family
Burner pressure for nominal heat input
11-4/1
14-4/1
Natural gas 2E (G20)
1.12 kPa (11.2 mbar)
1.38 kPa (13.8 mbar)
Natural gas 2E+ (G25)
1.48 kPa (14.8 mbar)
1.85 kPa (18.5 mbar)
Liquid gas 3P (G31)
3.17 kPa (31.7 mbar)
3.45 kPa (34.5 mbar)
E
Inspection and maintenance interval
The table below lists the manufacturer requirements with respect to minimum inspection and maintenance intervals. If na-
tional regulations and directives require shorter inspection and maintenance intervals, you should observe these instead of
the intervals listed. Each time inspection and maintenance work is carried out, carry out the required preparatory and com-
pletion work.
#
Maintenance work
Interval
1
Remove any dirt from the product
Annually
2
Check the flue gas sensor for dirt and damage. Checking that the flue
gas sensor is working correctly by completely blocking the flue gas with
flue gas restrictors
Annually
3
Checking the safety cut-out for dirt and damage
Annually
4
Cleaning the burner
If required, at least every
2 years
16
5
Cleaning the heat exchanger
If required, at least every
2 years
18
6
Cleaning the injector rail
If required, at least every
2 years
16
7
Cleaning the down-draught diverter
If required, at least every
2 years
17
8
Check the ignition electrode and thermocouple for damage, and replace
any bent and damaged components
Annually
9
Checking the seals on the test nipples for damage and replacing any
damaged seals
Annually
10
Checking that the water flow switch (micro switch) is working correctly
Annually
11
Carry out a test operation on the product, incl. domestic hot water gener-
ation
Annually
12
Checking leak-tightness
Annually
14
13
Checking the heat input
Annually
18
14
Check the flame pattern. Flames must not touch the heat exchanger shaft
If required, at least every
2 years
15
Visually inspecting the test nipples and hoses
Annually
16
Interrupt the thermocurrent by disconnecting the connection between the
thermocouple and holding magnet. The product must be shut down
Annually
17
Checking the water valve
If required, at least every
2 years
18
18
Logging flue-gas measured values and any maintenance work that was
carried out
Annually
19
Checking the product to see if flue gas is escaping at the down-draught
diverter, with the doors and windows closed and the casing installed
Annually