13

Operating manual atmoCRAFT

The unit can only be re-started if the heating system has 
sufficient water in it (see Section 4.8.7).

 Caution!

If the fault signal F.20 is shown repeatedly, an 
authorised heating engineer must be consulted 
to carry out a check of the system.

4.8.3 Ignition problems

1

Fig. 4.13  Fault resolution

If the burner fails to ignite after three attempts, the 
device does not start up and switches to "

Fault"

. This is 

indicated by the fault code 

"F.28"

 or 

"F.29"

 in the 

display.
•  First check whether the  stop-cock in the gas line is 

open.

Automatic ignition can only take place after you 
manually reset the fault.
•  To reset the fault, press the "reset" button (

1

) and hold 

it down for approx. one second.

 Caution!

Inappropriate alterations can cause damage!
If your gas boiler still does not start after the 
third attempt, you must call a suitably qualified 
heating engineer for help.

4.8.4 Fault caused by exceeding the temperature

1

2

Abb. 4.14 Releasing after STB switch-off

Your boiler is equipped with a safety temperature limiter 
(STB) which automatically switches off the boiler if the 
temperature gets too hot. This fault is displayed by the 
fault code 

"F.20"

.

•  Remove the front cover.
•  Release the STB by pushing the pin (

1

).

•  Reset the electronic system by pushing the "Reset" 

button (

2

).

 Caution!

If the fault signal F.20 is shown repeatedly, an 
authorised heating engineer must be consulted 
to carry out a check of the system.

4.8.5 Faults with the exhaust gas removal

The Vaillant atmoCRAFT units can be equipped with an 
exhaust gas sensor (accessories). If the exhaust gases 
are not removed properly, the unit switches off 
temporarily in order to prevent the escape of exhaust 
gas into the room where the boiler is located.
The display shows the symbol "Fault in air/exhaust gas 
route". The unit starts up again automatically after 
approx. 15-20 minutes after this switch-off.
After repeated switch-off (max. three failed attempts) 
the unit does not start up again. The error message 
"

F.36

" appears in the display.

Operation 4

GB

Summary of Contents for atmoCRAFT VK SERIES

Page 1: ...VK 654 9 1654 9 atmoCRAFT DE AT GB CZ SK HU PL HR SI SCG...

Page 2: ...For the owner VK 654 9 1654 9 Operating manual atmoCRAFT Gas heating boiler GB...

Page 3: ...by exceeding the temperature 13 4 8 5 Faults with the exhaust gas removal 13 4 8 6 Filling unit heating installation 14 4 9 Shut down 14 4 10 Frost protection 15 4 10 1 Frost protection function 15 4...

Page 4: ...4 Data badge The identification plate is included with the burner and should be mounted on the separation wall 2 Safety What to do in an emergency Danger If you smell gas risk of poisoning and explos...

Page 5: ...sufficiently heated Caution Risk of damage If there is a power cut or if the room temperature is set too low in individual rooms it cannot be ruled out that sections of the heating system are damaged...

Page 6: ...en by the heating engineer The desired heating and set back phases e g at night are automatically turned on and off using the integrated time programmes Weather compensators combined with thermostat v...

Page 7: ...0 C also lead to increased lime scale production Energy conscious use of water Energy conscious use of water can reduce your bills considerably For example taking a shower instead of a bath whereas ab...

Page 8: ...nk temperature in normal mode if a storage tank sensor is connected 6 button for moving backwards in the display for adjustment and troubleshooting by the engineer 7 Reset button for resetting certain...

Page 9: ...0 6 5 4 3 bar 1 Fig 4 4 Checking the filling pressure of the heating installation pressure gauge not included Check the filling pressure of the installation using the pressure gauge 1 not included For...

Page 10: ...ng feed temperature Note We recommend a setting of 60 C for economic and hygienic reasons e g Legionella Caution Danger of calcium deposit build up If your water hardness is more than 1 79 mol m3 10 d...

Page 11: ...m fitted to your heating system 4 5 2 Setting the flow temperature no controller connected 1 2 Fig 4 8 Feed temperature setting without heating controller If there is no external controller set the fl...

Page 12: ...tion of your boiler Press the i button 1 to activate the status displays The display 2 then shows the individual status codes e g S 4 for burner operation The table below explains the most important s...

Page 13: ...he heating system see Section 4 8 2 Is there an ignition problem see Section 4 8 3 Hot water operation no problem Heating does not start Is there a requirement for heating from the external controller...

Page 14: ...exceeding the temperature 1 2 Abb 4 14 Releasing after STB switch off Your boiler is equipped with a safety temperature limiter STB which automatically switches off the boiler if the temperature gets...

Page 15: ...However in exceptions the water quality might not be suitable for filling in the heating system heavily corrosive or extremely calciferous water In a case such as this you should please contact your a...

Page 16: ...he frost protection system cannot guarantee flow through the entire heating system 4 10 2 Frost protection by draining Another way to protect the heating system and the appliance from frost is to drai...

Page 17: ...ed as follows to perform the measurements Activate the chimney sweep mode by simultaneously pushing the buttons 6 and 7 on the DIA System The measurements should be taken at the earliest after 2 minut...

Reviews: