16 • vacon
commissioning
Tel: +358-201-2121 • Fax: +358-201-212 205
5
5.2 Start-up
test
Frequency converter application
Choose Fieldbus
(Bus/Comm)
for the active control place (see Vacon NX User's Manual, Chapter
7.3.3).
Master software
1. Write 100.0 1 to
nviDrvSpeedStpt
.
2. Frequency converter status is RUN and output frequency is 1.00 *
nviDrvSpeedScale
3. Write 0.0 0 to
nviDrvSpeedStpt
4. Frequency converter status is STOP.
If nvoDrvStats bit 3 = 1 Status of frequency converter is FAULT.