lonworks interface
vacon
• 23
24-hour service: +358-40-8371 150
•
Email: [email protected]
6
nvoDrvSpeed
This output network variable provides the speed of the drive as a percentage of the nominal speed.
nvoDrvCurnt
This output network variable provides the drive output current in amperes.
nvoDrvPwr
This output network variable provides the drive output power in kW.
nvoDrvRunHours
This output network variable provides the drive resettable operation time counter for the motor in
running hours. The maximum value for used SNVT is 65535 h. On the frequency converter the value
can go much higher. If the counter exceeds the SNVT’s maximum value, the network variable stays at
its maximum. In such cases the real value can be seen on Vacon NX’s operating keypad.
nvoDrvStatus
This output network variable provides the drive status.
Bit Description
Value = 0
Value = 1
0
Not Ready
Ready
1
FC stopped
Running
2
Clockwise Counterclockwise
3
No fault
Fault active
4
No warning
Warning active
5
Reference
≠
Actual value
Reference = Actual value
Table 6-8. Status word bit descriptions
nvoDrvEnrgy
This output network variable provides the drive resettable energy consumption counter. The
maximum value for used SNVT is 65535 kWh. On the frequency converter the value can go much
higher. If the counter exceeds the SNVT’s maximum value, the network variable stays at its
maximum. In such cases the real value can be seen on Vacon NX’s operating keypad.
nvoActFault
This output network variable provides the drive active fault code.
If the value is 0 the frequency
converter has no fault. See the fault code list in Vacon NX Frequency Converter User’s Manual for
fault identification.
nvoProcessOut1..8
These output network variables are sent directly from the application (see more detailed explanation
in chapter 6.5 Process data) The valid range is 0 to 65535 (-163,840 to 163,835).