Fault codes and software
24h on-call service phone: +358 (0)40 83 71 150
32
4
navigation. When pressing again the arrow left over 5 s, the active control place
jumps back to I/O or Fieldbus.
10. 3. 2. 11. NXS00001V170
Replaced version: NXS00001V169.VCN
System software version: 11.73.8480
Changes in applications:
•
All applications made with new project tool NC1131-3.
•
When motor identification-run was done by using PC control, the drive did not
accept new start command from PC until stop command was send even that drive
was automatically already stopped after id-run sequency.
•
Help text is added for status word-signal when monitoring with NCDrive.
•
Local/Remote Control application: All 3 pcs. Pt100 temperature values from Pt100
option board (B8) are separately displayed on monitoring page (V1.21.8, 1.21.9
and 1.21.10). ID numbers are given for them as well (ID50, 51 & 52) i.e tempera-
tures can be read for example via Profibus.
•
Multi purpose application: ID numbers are given also for counter calues to make
possible reading and resetting via fieldbusses. PowerOnTimeTripcounter, PowerOn-
TripCounterUnit and ResetOnTimeTripCounter = ID10, 1050 & 1051. EnergyMeter,
EnergyMeterFormat and EnergyMeterUnit = ID11, 80 &81. EnergyTripCounter,
EnergyTripCounterUnit and ResetMWhTripCounter = ID12, 1052 & 1053.
•
Multi purpose application: ID value added for active warning = ID74
10. 3. 2. 12. NXS00001V171
Replaced version: NXS00001V170.VCN
System software version: 11.74.8486
Changes in system software:
•
Currentcutter functionality is changed in FR7 500V and FR8 500V drives.
10. 3. 2. 13. NXS00001V172
Replaced version: NXS00001V171.VCN
System software version: 11.75.8546
Changes in system software:
•
The card description for OPTICI (Ethernet option board) is changed to be able to do
the IP addressing using keypad. The parameters are visible automatically in the
Expander boards menu.