Page 4 (15)
Vacon
I/O-expander board installation (Vacon CXS-range)
Vacon Plc
Tel:
+358-201 2121
Fax:
+358-201 212 205
Service:
+358-40-8371 150
E-mail:
[email protected]
http://www.vacon.com
2
SPECIFICATIONS
Safety
Fulfills EN50178, C-UL and EN60204-1 standards
Control
Analogue voltage, input
0—± 10 V, R
i
≥
200 k
Ω
connections
Analogue current, input
0(4)—20 mA, R
i
= 250
Ω
Digital input
24 V: "0"
≤
10 V, "1"
≥
18 V, R
i
> 5 k
Ω
Aux. voltage
24 V (±20%), max. 50 mA
Reference voltage
10 V ±3 %, max. 10 mA
Analogue current, output
0(4)—20 mA, R
L
= 500
Ω
, resolution 10 bit,
accuracy
≤
±2%
Analogue voltage, output 0(2)—10 V, R
L
≥
1 k
Ω
, resolution 10 bit,
accuracy
≤
±2%
Relay output
Max. switching voltage:
300 V DC, 250 V AC
Max. switching load:
8A / 24 V DC
0,4 A / 300 V DC
2 kVA / 250 V AC
Max. continuous load:
2 A rms
Thermistor input
R
trip
= 4.7 k
Ω
Encoder input
24 V: "0"
≤
10 V, "1"
≥
18 V, R
i
= 2.2 k
Ω
5 V: "0"
≤
2 V, "1"
≥
3 V, R
i
= 330
Ω
Table 2-1 Specifications. (All the control connections are not found on every I/O-expander board, for
specific information see Chapters 1 and 4.)
The control connections are isolated from the mains potential and the I/O ground is
connected to the frame of the inverter via a 1-M
Ω
resistor and 4,7-nF capacitor*). The
control I/O ground can be connected directly to the frame by changing the position of the
jumper X4 (GND ON/OFF) to the ON-position. Digital inputs and relay outputs are also
isolated from the I/O ground.
*) Default value (X4 is GND OFF- position).
NOTE!
Internal components and circuit boards (except the isolated I/O terminals) are at
mains potential when the frequency converter is connected to the mains. This
voltage is extremely dangerous and may cause death or severe injury if you
come into contact with it.
The control I/O terminals are isolated from the mains potential, but the relay
outputs and other I/O's may have a dangerous voltage connected even if the
power is disconnected from the frequency converter.