Page 12 (15)
Vacon
I/O-expander board installation (Vacon CXS-range)
Vacon Plc
Tel:
+358-201 2121
Fax:
+358-201 212 205
Service:
+358-40-8371 150
E-mail:
[email protected]
http://www.vacon.com
Terminal
Signal
Description
206
+24V
Control voltage output
Voltage for switches, etc. max. 50 mA
207
GND
I/O ground
Ground for reference and controls
208
CMC
Common for DIC1-DIC5
Connect to GND or + 24 V
209
DIC1
External fault
Contact open = no fault
(closing contact)
Contact closed = fault
210
DIC2
Run disable
Cont. open = start of motor enabled
Cont. closed= start of motor disabled
211
DIC3
Acceler. / Decel. time
Contact open = time 1 selected
selection
Contact closed = time 2 selected
212
DIC4
Jogging speed selection
Contact open = no action
Contact closed = jogging speed
213
DIC5
Fault reset
Contact open = no action
Contact closed = fault reset
214
N.C.
Not connected
215
N.C.
Not connected
221
T I +
Thermistor input
222
T I +
225
RO4/1
Relay output 4
RUN
226
RO4/2
4.2
Vacon CX101OPT
Signal from
motor thermistors *)
*) NOTE!
Thermistor input (terminals 221 and 222) must be shorted if not used.
Figure 4-2 Control connections of Vacon CX101OPT.