![Vacon 100X series Installation, Technical And Maintenance Manual Download Page 65](http://html2.mh-extra.com/html/vacon/100x-series/100x-series_installation-technical-and-maintenance-manual_3123117065.webp)
Technical data
vacon • 63
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
7
7.
T
ECHNICAL
DATA
7.1
AC drive power ratings
7.1.1
Mains voltage 3AC 208-240V
NOTE:
The rated currents in given ambient temperatures (in Table 28) are achieved only when the
switching frequency is equal to or less than the factory default.
Table 28. Power ratings of VACON
®
100 X, supply voltage 3AC 208-240V.
Mains voltage 3AC 208-240V, 50/60 Hz
AC drive
type
Input
current
[A]
Loadability
Motor shaft power
230V supply
Rated continuous
current IN
[A]
50% overload
current
[A]
Max current
IS
[kW]
[HP]
MM4
0007
6.0
6.6
9.9
13.2
1.1
1.5
0008
7.2
8.0
12.0
16.0
1.5
2.0
0011
9.7
11.0
16.5
22.0
2.2
3.0
0012
10.9
12.5
18.8
25.0
3.0
4.0
MM5
0018
16.1
18.0
27.0
36.0
4.0
5.0
0024
21.7
24.2
36.3
48.4
5.5
7.5
0031
27.7
31.0
46.5
62.0
7.5
10.0
MM6
0048
43.8
48.0
72.0
96.0
11.0
15.0
0062
57.0
62.0
93.0
124.0
15.0
20.0