Mounting
vacon • 27
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
3
3.6
Cooling
The AC drive produces heat in operation and is cooled down by air circulated by a fan. The cooling
concept is independent of the motor fan.
Enough free space must be left around the AC drive to ensure sufficient air circulation and cooling.
Different acts of maintenance may also require a certain amount of free space.
The minimum clearances given in Table 10 must not be exceeded. It is also important to ensure that
the temperature of the cooling air does not exceed the maximum ambient temperature of the drive.
Contact local VACON
®
distributor for more information on required clearances in different instal-
lations.
Table 10. Min. clearances around AC drive.
A = Clearance left and right from the drive
B = Clearance above the drive
C = Clearance underneath the AC drive
Figure 16. Installation space.
Should you need further details on the cooling system of the VACON
®
100 X, please contact your
local VACON
®
distributor.
Min clearance [mm]
Type
A
B
C
All types
80
160
60
Table 11. Required cooling air.
Type
Cooling air required
[m
3
/h]
MM4
140
MM5
140
MM6
280