Power cabling
vacon • 35
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
4
The terminal sizes are intended for 1 conductor. For MM6, the max. diameter of the ring terminal is 14 mm.
The cable dimensioning is based on the criteria of the International Standard
IEC60364-5-52
: Cables must be
PVC-isolated; Max number of parallel cables is 9.
When using cables in parallel,
NOTE HOWEVER
that the requirements of both the cross-sectional area and
the max number of cables must be observed.
For important information on the requirements of the grounding conductor, see chapter Grounding and earth
fault protection of the standard.
For the correction factors for each temperature, see International Standard
IEC60364-5-52
.