Power cabling
vacon • 41
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
4
Tightening torques of cable glands:
UL installation:
Figure 27.Cable entry plate, MM4 UL installation.
Table 19. Tightening torque and dimension of cable glands.
Enclosure
size
Gland screw
type [metric]
Tightening torque [Nm]/[lb-in.]
[Nm]
lb-in.
MM4
M16
1.0
8.9
M25
4.0
35.5
MM5
M16
1.0
8.9
M25
4.0
35.5
M32
7.0
62.1
MM6
M16
1.0
8.9
M25
4.0
35.5
M40
10.0
88.7
6
•
To connect NPT pipes to VACON
®
100 X, use the optional metal cable entry
plate (included in -R02 option) to meet UL installation rules.
•
One metal conduit plate with accessories (screws and gasket) is delivered in a
separate bag together with the drive. See the following figures for more
details.