3.2.5 General cabling rules
1
Before starting the installation, check that none of the components of the fre-
quency converter is live.
2
Place the motor cables sufficiently far from other cables:
•
Avoid
placing the motor cables in long
parallel lines
with other cables.
• If the motor cable runs in parallel with other cables, the
minimum distance
between the motor cable and other cables is
0.3 m
.
• The given distance also applies between the motor cables and signal cables
of other systems.
• The
maximum length
of the motor cables for MI1-3 is
30 m
. If use longer
cable, current accuracy will be decreased.
• The
motor cables
should cross other cables at an angle of
90 degrees
.
3
If cable insulation checks are needed, see Chapter Cable and motor insulation
checks.
4
Connecting the cables:
• Strip the motor and mains cables as advised in Figure Stripping of cables.
• Connect the mains, motor and control cables into their respective termi-
nals, see Figures Vacon 10 power connections, MI1 - Install the control
cables.
• Note the tightening torques of
power cables and
control cables
given in
Vacon 10 power connections, MI1 and Install the control cables. MI1 - MI3.
See Chapter6.2.
• For information on cable installation according to UL regulations see Chap-
ter Cable installation and the UL standards.
• Make sure that the control cable wires do not come in contact with the elec-
tronic components of the unit.
• If an
external brake resistor
(option) is used, connect its cable to the appro-
priate terminal.
•
Check the connection
of the earth cable to the motor and the frequency
converter terminals marked with.
• Connect the
separate shield of the motor cable to the earth plate
of the
frequency converter, motor and the supply centre.
Summary of Contents for 10
Page 1: ......
Page 17: ...14 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 3P 230 V POWER LOSS ...
Page 18: ...installation vacon 15 24 hour support 0 201 212 575 Email vacon vacon com 3 ...
Page 19: ...16 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 1P 230 V POWER LOSS ...
Page 20: ...installation vacon 17 24 hour support 0 201 212 575 Email vacon vacon com 3 ...