10.2.4 Vacon 10 – Mains voltage 575 V
Note 1:
The input currents are calculated values with 100 kVA line transformer supply.
Note 2:
The mechanical dimensions of the units are given in Chapter 3.1.1.
10.3 Brake resistors
Vacon 10 type
Minimum brak-
ing resistance
Resistor type code (from Vacon NX family)
Light duty
Heavy duty
Resistance
MI2 204-240V,3~
50 Ohm
-
-
-
MI2 380-480V,3~
118 Ohm
-
-
-
MI3 204-240V, 3~
31 Ohm
-
-
-
MI3 380-480V, 3~
55 Ohm
BRR-0022-LD-5
BRR-0022-HD-5 63 Ohm
MI3 575V, 3~
100 Ohm
BRR-0013-LD-6
BRR-0013-HD-6 100 Ohm
Note!
For MI2 and MI3, only 3-phase units are equipped with brake chopper.
For further information on brake resistors, please download Vacon NX Brake Resis-
tor Manual (UD00971C) on http://www.vacon.com / Support & Downloads
Mains voltage 575 V, 50/60 Hz, 3~ series
Freq.
converter
type
Rated loadability
Motor shaft
power
Nominal
input
current
Mechanical
size
Weight
(kg)
100% contin.
current I
N
[ A ]
150% over-
load current
[ A ]
P
[ HP ]
P
[ kw ]
[ A ]
0002
1,7
2,6
1
0,75
2
MI3
0,99
0003
2,7
4,2
2
1,5
3,6
MI3
0,99
0004
3,9
5,9
3
2,2
5
MI3
0,99
0006
6,1
9,2
5
3.7
7,6
MI3
0,99
0009
9
13,5
7.5
5,5
10,4
MI3
0,99
Table 10.6: Vacon 10 power ratings, 575 V
Summary of Contents for 10
Page 1: ......
Page 17: ...14 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 3P 230 V POWER LOSS ...
Page 18: ...installation vacon 15 24 hour support 0 201 212 575 Email vacon vacon com 3 ...
Page 19: ...16 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 1P 230 V POWER LOSS ...
Page 20: ...installation vacon 17 24 hour support 0 201 212 575 Email vacon vacon com 3 ...