68
•
vacon
parameter descriptions
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
9
1 = Ramping
After the Stop command, the speed of the motor is decelerated ac-
cording to the set deceleration parameters.
If the regenerated energy is high it may be necessary to use an exter-
nal braking resistor for to be able to decelerate the motor in accepta-
ble time.
2.4
I / O
START
STOP
LOGIC
Values 0...3 offer possibilities to control the starting and stopping of the AC
drive with digital signal connected to digital inputs. CS = Control signal.
The selections including the text 'edge' shall be used to exclude the possibility
of an unintentional start when, for example, power is connected, re-connected
after a power failure, after a fault reset, after the drive is stopped by Run En-
able (Run Enable = False) or when the control place is changed to I / O control.
The Start / Stop contact must be opened before the motor can be started.
Accurate stop mode is that the stop time is fixed from falling edge of DI to mo-
tor stop.
Selection
number
Selection name
Note
0
CS1:Forward
CS2:Backward
The functions take place when the contacts are closed.
Figure 9.3: Start/Stop logic, selection 0
FWD
REV
Set
frequency
Set
frequency
0 Hz
Run enable
Ctrl signal 1
Ctrl signal 2
Keypad
start button
Keypad
stop button
1
2
3
4
5
6
7
8
9
10
11
12
13
Output
frequency
t
Summary of Contents for 10
Page 1: ......
Page 17: ...14 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 3P 230 V POWER LOSS ...
Page 18: ...installation vacon 15 24 hour support 0 201 212 575 Email vacon vacon com 3 ...
Page 19: ...16 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 1P 230 V POWER LOSS ...
Page 20: ...installation vacon 17 24 hour support 0 201 212 575 Email vacon vacon com 3 ...