TZIDC, TZIDC-200
| COI/TZIDC/TZIDC-200-EN 33
4
Diagnosis / error messages
4.1
Error codes
Error code
Possible cause
Impact
Troubleshooting the Instrument
The supply voltage was interrupted for
at least 20 ms.
(This error is displayed after resetting the
device to indicate the reason for the
reset.)
.
g
n
ir
i
w
e
h
t
d
n
a
e
c
r
u
o
s
r
e
w
o
p
e
h
t
k
c
e
h
C
-
The supply voltage has fallen below the
minimum voltage.
The actuator is moved to the safe
position. After approx. 5 seconds, the
positioner is automatically reset and
starts up again with the message
ERROR 10
. If a local communication
interface (LCI) is plugged in, the device
will enter the operating mode LCI
supply.
Check the power source and the wiring.
The position is outside the measuring
range. Possible reason is a malfunction
in the position sensor.
In c ontrol mode:
The actuator is moved to the safe
position.
On the configuration level:
The output is set to neutral until a button
is pressed. After approx. 5 seconds the
positioner is automatically reset in
control mode and on the con
fi
guration
level.
Check the mounting.
Invalid input current.
This display indicates when the setpoint
signal is overridden. The actuator is
moved to the safe position.
.
g
n
ir
i
w
e
h
t
d
n
a
e
c
r
u
o
s
r
e
w
o
p
e
h
t
k
c
e
h
C
-
No access possible to the data in the
EEPROM.
The actuator is moved to the safe
position. After approx. 5 seconds, the
positioner is automatically reset.
Attempts are made to restore the data.
This compensates for intermittent errors
in the communication environment with
the EEPROM.
If there is still no access to the EEPROM
data after resetting the device, load the
factory settings. If the error still persists,
the device must be returned for repair to
the manufacturer.