Parameter group 11: Safe position
3.15.1
FAIL_POS – Safe position
This parameter must be used to activate the safe position prior
to loading the factory settings (parameter
FACT_SET
) or
changing the I/P module type (parameter I
IP-TYP
).
NOTE
After setting parameters
FACT_SET
and
IP-TYP
as required,
the safe position must be deactivated again manually.
The safe position that is activa ted (i.e., whether the actuator is
ventilated or blocked) depends on the I/P module installed.
Activating / deactivati ng the safe position:
Press and hold
ENTER
until the displayed countdown from 3
to 0 is
fi
nished. Then release
ENTER
.
The safe position is activated or deactivated, respectively.
3.15.2
FACT_SET – Factory setting
You can use this parameter to reset the positioner to the
factory setting. This is necessary, e.g., if an already con
fi
gured
positioner has to be installe d on a di
ff
erent actuator and
subsequently recon
fi
gured.
CAUTION
Risk of injury!
For safety reasons, after loading the factory settings you
must check whether the I/P module type that is set matches
the actual I/P module type present in the device.
Otherwise dangerous situations may occur when operating in
control mode. It may happen that the actuator is driven at full
speed to the end position.
NOTE
You can only load the factory sett ings when the actuator is in
the safe position (parameter
FAIL_POS
). Otherwise, this
action is inhibited and the message
NO_F_POS
is indicated
in the display.
If you save the settings in the non-volatile memory after
loading the factory settings, operating mode 1.3 is
automatically activated on the operating level.
Load factory settings:
Press and hold
ENTER
until the displayed countdown from 3
to 0 is
fi
nished.
The positioner is reset to th e factory settings. The message
COMPLETE
is displayed.
Press
ENTER
to acknowledge the message.
Selection
FS_LOAD
Loads the factory settings
con f
mA
%
C
°
conf
mA
%
C
°
conf
mA
%
C
°