Fault code 01, 02, 03, 11, 12, 13 

or 41

 

is displayed on the LCD and 

the alarm is continuously 

sounding. 

A  UPS  internal  fault  has 

occurred.  There  are  two 
possible results: 

1. The load is still supplied, 

but directly from AC power 
via bypass.   

2.  The  load  is  no  longer 

supplied by power.   

Contact  your  reseller  or 

[email protected] 

Battery backup time is shorter 

than nominal value. 

Batteries have not been 

fully charged 

Charge the batteries for at 

least 5 hours and then 
check capacity. If the 

problem persists, consult 

your reseller, or contact 
[email protected] 

Possible batteries defect 

Contact your reseller or 

[email protected] 

Fault code 2A is displayed on the 
on LCD and the alarm is 

continuously sounding. 

A short circuit of the 
charger output has 

occurred. 

Check the wiring of a 
connected external battery 

pack for short-circuited 

Fault code 45 is displayed on the 
on the LCD display and the alarm 

is continuously sounding. 

No charger output and 
battery voltage is less than 

10V/PC. 

Contact your reseller or 
[email protected] 

 

4. Storage and Maintenance 

 

The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 

25°C ambient temperature) has been exceeded, the batteries must be replaced. Contact your 
reseller or [email protected].   

 

 
 

 

Storage   

Prior to storing, charge the UPS for 5 hours. Store the UPS covered and upright in a cool, 
dry location. To protect battery performance and limit degradation, recharge the battery 
in accordance with the following table: 

 

Storage Temperature 

Recharge Frequency 

Charging Duration 

-25°C - 40°C 

Every 3 months 

1-2 hours 

40°C - 45°C 

Every 2 months 

1-2 hours 

 
 
 
 
 

Be sure to deliver the spent battery to a recycling facility or ship it to your 

dealer in the replacement battery packing material. 

 

 

 

Summary of Contents for UPS2URM3000DC-NC-1N

Page 1: ...UPS2URM3000DC NC 1N User Guide...

Page 2: ...Modem surge protection 5 USB communication port 6 RS 232 communication port 7 SNMP intelligent port 8 Emergency power off function connector EPO 9 External battery connection not supported 1 1 Operat...

Page 3: ...t connecting battery wires Before installation of the UPS please follow the steps below to re connect the battery wires Rack Mount Installation Caution DO NOT use the mounting brackets to lift the uni...

Page 4: ...mm in the rear of the UPS Operate at or below a maximum altitude of 3000m for normal operation at full load 2 UPS input connection Plug the UPS into a two pole three wire grounded receptacle only Avoi...

Page 5: ...ing software installed you can schedule UPS shutdown start up and monitor UPS status through PC The UPS is equipped with an SNMP Network card When installing either SNMP for advanced communications an...

Page 6: ...power to change the batteries press the OFF button on the front panel for two seconds to power off the UPS and switch off utility power where the UPS is connected DO NOT DISCONNECT the batteries while...

Page 7: ...rior to connecting or disconnecting battery terminals Remove battery grounds during installation and maintenance to reduce the risk of shock Remove the connection from ground if any part of the batter...

Page 8: ...onfirm selection in UPS setting mode Select Button Switch LCD message Press this button to change the LCD message for input voltage input frequency input current battery voltage battery current batter...

Page 9: ...oad current and load percent k kilo W watt V voltage A ampere percent centigrade degree Hz frequency Load information Indicates the load level by 0 24 25 49 50 74 and 75 100 Indicates overload Program...

Page 10: ...lay content Meaning ENA Enable DIS Disable ESC Escape HLS High loss LLS Low loss AO Active open AC Active close EAT Estimated autonomy time RAT Running autonomy time SD Shutdown OK OK ON ON BL Battery...

Page 11: ...125VAC 127 presents output voltage is 127VAC 127VAC is not applicable in US region l 02 Frequency Converter enable disable Interface Setting Parameter 2 Enable or disable converter mode CF ENA convert...

Page 12: ...eptable high voltage point and acceptable low voltage point for Bypass mode by pressing the Down key or Up key HLS Bypass high voltage point For 100 110 115 120 125 127VAC models 120 140 Set the high...

Page 13: ...or programmable outlets which connect to non critical devices on battery mode Default 999 l 11 Autonomy limitation setting Interface Setting Parameter 2 Set the backup time on battery mode for general...

Page 14: ...o 2 40V cell Default 2 36V cell l 15 Charger float voltage setting Interface Setting Parameter 2 Set the charger float voltage 2 20 2 33 Set the charger float voltage from 2 20 V cell to 2 33V cell De...

Page 15: ...he UPS will bypass voltage to output for energy saving The UPS also charges the battery in ECO mode Frequency Converter mode When input frequency is within 40 Hz to 70 Hz the UPS can be set to a const...

Page 16: ...Over input current Sounds 2 beeps every 10 seconds Battery is not connected Sounds every 2 seconds Over Charge Sounds every 2 seconds Site wiring fault Sounds every 2 seconds EPO enable Sounds every 2...

Page 17: ...t v7 world com Fault code 28 is displayed on the LCD and the alarm is continuously sounding Battery voltage is too low or there is a charger fault Contact your reseller or techsupport v7 world com The...

Page 18: ...ing of a connected external battery pack for short circuited Fault code 45 is displayed on the on the LCD display and the alarm is continuously sounding No charger output and battery voltage is less t...

Page 19: ...aveform Batt Mode Pure Sinewave EFFICIENCY AC Mode 91 full charged battery ECO Mode 96 full charged battery Battery Mode 90 BATTERY Battery Type 12V 9AH Number 6 Recharge Time 3 hours recover to 95 ca...

Page 20: ...or near heat sources l Avoid blocking ventilation holes in the UPS enclosure 7 3 Installation l Do not connect appliances or devices which can overload the UPS system e g laser printers l Route cables...

Page 21: ...electrically live and dangerous l Before carrying out any kind of service and or maintenance disconnect the batteries and verify that no current is present and no hazardous voltage exists in the termi...

Reviews: