12
49Hz. (Default: 47Hz)
For 60Hz output frequency models:
55-59Hz:
Set the frequency low loss point from 55Hz to
59Hz. (Default: 57Hz)
l
09: Programmable outlets enable/disable
Interface
Setting
Parameter 2:
Enable or disable programmable outlets.
ENA:
Programmable outlets enable
DIS:
Programmable outlets disable (Default)
l
10: Programmable outlets setting
Interface
Setting
Parameter 2:
Set the backup time limits for programmable
outlets.
0-999:
Set the backup time limits in minutes from 0-999 for
programmable outlets which connect to non-critical devices
on battery mode. (Default: 999)
l
11: Autonomy limitation setting
Interface
Setting
Parameter 2:
Set the backup time on battery mode for
general outlets.
0-999:
Set the backup time in minutes from 0-999 for
general outlets on battery mode.
DIS:
Disable the autonomy limitation and the backup time
will depend on battery capacity. (Default)
Note:
Setting to “0”, sets backup time to just 10 seconds.
l
12: Battery total AH setting
Interface
Setting
Parameter 2:
Set the battery total AH of the UPS.
7-999:
Setting the battery total capacity from 7-999 in AH.
Please set the correct battery total capacity if external
battery bank is connected.