11
l
05: ECO voltage range setting
Interface
Setting
Parameter 2:
Set the acceptable high voltage point and
low voltage point for ECO mode by pressing Down key or Up
key.
HLS:
High loss voltage in ECO mode in parameter 2.
For 100/110/115/120/125/127VAC models, the setting
range in parameter 3 is from +3V to +12V of the nominal
voltage. (Default: +6V)
LLS:
Low loss voltage in ECO mode in parameter 2.
For 100/110/115/120/125/127VAC models, the setting
voltage in parameter 3 is from -3V to -12V of the nominal
voltage. (Default: -6V)
l
06: Bypass enable/disable when UPS is off
Interface
Setting
Parameter 2:
Enable or disable Bypass function.
ENA:
Bypass enable
DIS:
Bypass disable (Default)
l
07: Bypass voltage range setting
Interface
Setting
Parameter 2:
Set the acceptable high voltage point and
acceptable low voltage point for Bypass mode by pressing
the Down key or Up key.
HLS:
Bypass high voltage point
For 100/110/115/120/125/127VAC models:
120-140:
Set the high voltage point from 120VAC to
140VAC. (Default: 132VAC)
LLS:
Bypass low voltage point
For 100/110/115/120/125/127VAC models:
85-115:
Set the low voltage point from 85VAC to 115VAC.
(Default: 85VAC)
l
08: Bypass frequency range setting
Interface
Setting
Parameter 2:
Set the acceptable high frequency point and
acceptable low frequency point for Bypass mode by pressing
the Down key or Up key.
HLS:
Bypass high frequency point
For 50Hz output frequency models:
51-55Hz:
Set the frequency high loss point from 51Hz to
55Hz. (Default: 53Hz)
For 60Hz output frequency models:
61-65Hz:
Set the frequency high loss point from 61Hz to
65Hz. (Default: 63Hz)
LLS:
Bypass low Frequency point
For 50Hz output frequency models:
45-49Hz:
Set the frequency low loss point from 45Hz to