background image

ENGLISH

36

SAFETY RIBBONS

The control unit considers two kinds of safety ribbons,
depending on the terminal to which they are connected:

Type 1 (fixed): 

they are mounted on walls or on other fixed

obstacles that are approached by the gate doors during the
opening phase. When type 1 safety ribbons operate during
the gate opening phase, the control unit will close the doors
for 3 seconds, then it stands still; when type 1 safety ribbons 
operate during the gate closing phase, the control unit will 
stand still immediately. The direction of the gate at next 
command of START or PEDESTRIAN START depends upon the 
parameter STOP (it inverts or continues the motion). 
If the input STOP is disabled, the command makes the motion 
continue in the same direction.

Type 2 (mobile): 

they are mounted to the door ends.

When type 2 safety ribbons operate during the gate opening
phase, the control unit will stand still immediately; when
type 2 safety ribbons operate during the gate closing, the
control unit will open the doors for 3 seconds, then it will
stand still. The direction of the gate at next command of
START or PEDESTRIAN START depends upon the parameter
STOP (it inverts or continues the motion). If the input STOP
is disabled, the command makes the motion continue in the
same direction.

Both the input can manage the classic safety edge with n.c.
contact and the conductive rubber safety edge with 8,2 kohm
nominal resistance.

In addition, the V2 wireless edge system may be managed (see
the instructions provided with the device).

Connect type 1 safety ribbons cables between terminals 

P9 

and

P11 

of the control unit.

Connect type 2 safety ribbons cables between terminals 

P10

and 

P11 

of the control unit.

In order to meet the requirements of the EN12978 rules, it is
necessary to install safety edges controlled by a control unit
continuously checking the proper working. If using control units
suited to the test by power outage, connect the power supply
cables of the control unit between terminals 

P13

and 

P14

of the

control unit. 
Otherwise, connect them between terminals 

P12

and 

P13

.

m

WARNING:

• Make use of safety ribbons having outputs with normally

close contact.

• Outputs of same kind safety ribbons must be connected in

series.

PHOTOCELLS

The control unit considers two kinds of photocells, depending on
the terminal to which they are connected:

Photocell 1:

that is to say, photocells installed on the gate 

inner side, which are active both during the opening and the 
closing phase. When photocells 1 operate, the control unit 
stops the gate; as soon as the photocell beam is free, the 
control unit will open the gate completely.

m

WARNING: 

Type 1 photocells must be installed so that

they completely cover the opening area of the gate.

Photocell 2:

that is to say, photocells installed on the 

external gate side and which are active during the closing
phase only. When photocells 2 operate, the control unit 
opens the gate immediately, without waiting for release.

PD18

control unit supplies a 24VAC power supply to photocells

and it can perform a photocell operation test before starting the
gate opening phase. Photocell power terminals are protected by
an electronic fuse that stops current in case of overload.

• Connect power supply cables of photocells transmitter 

between terminals 

P13

and 

P14

of the control unit.

• Connect power supply cables of photocells receiver 

between terminals 

P12

and 

P13

of the control unit.

• Connect receiver output of photocells 1 between terminals 

P7

and 

P11

of the control unit and receiver output of photocells 

2 between terminals 

P8

and 

P11

of the control unit. 

Use outputs having normally closed contact. 

m

WARNING:

• if several couples of same kind photocells are mounted, 

their outputs must be connected in series.

• In case of reflection photocells, power supply must be 

connected to terminals 

P13

and 

P14

of the control unit to 

carry out the operation test.

Summary of Contents for FORTECO

Page 1: ...LECTROMECANIQUE 230V IRREVERSIBLE A CREMAILLERE POUR PORTAILS COULISSANTS JUSQU A 2200 KG DE POIDS MOTOR ELECTROMECANICO 230V IRREVERSIBLES A CREMALLERA PARA PUERTAS CORREDERAS HASTA 2200 KG DE PESO I...

Page 2: ......

Page 3: ...Y 35 BLINKER 35 COURTESY LIGHT 35 PHOTOCELLS 36 SAFETY RIBBONS 36 STOP 37 ACTIVATION INPUTS 37 PLUG IN RECEIVER 37 EXTERNAL AERIAL 38 ADI INTERFACE 38 ELECTRIC CONNECTIONS TABLE 38 CONTROL PANEL 40 US...

Page 4: ...ans of a proper tool and adjusted according to the max limits which EN 12453 allows We recommend to make use of an emergency button to be installed by the automation connected to the control unit STOP...

Page 5: ...A Full load current 3 A 3 2 A 4 A Running capacitor 12 F 18 F 18 F Start off capacitor 12 F 14 F 14 F Gate maximum speed 0 16 m s 0 16 m s 0 16 m s Maximum thrust 900 N 1300 N 1550 N Duty cicle ambie...

Page 6: ...ated in the drawing for the foundations 2 Arrange for one or two pipes for the passage of electric cables 3 Assemble the 4 clamps on the anchoring plate and fix them with the 4 bolts issued with the m...

Page 7: ...ame height than the motor pinion The rack MUST BE positioned 1 or 2 mm over the pinion of the motor all the gate length WARNING If the gate is very heavy we suggest to use an M4 22x22 rack code 162324...

Page 8: ...rn clockwise until reached the limit switch To restore the automation proceed as follows 1 turn the key L anticlockwise until reached the limit switch then draw it out 2 turn the key K anticlockwise c...

Page 9: ...otocells safety ribbons and triacs before each opening Deactivation of safety inputs through the configuration menu no jumper is required for terminals concerning safety devices that have not been ins...

Page 10: ...king the proper working If using control units suited to the test by power outage connect the power supply cables of the control unit between terminals P13 and P14 of the control unit Otherwise connec...

Page 11: ...closed and it will immediately stop as the contact is open Timer mode it is similar to the standard mode but the gate stays open completely or partially while the contact is closed on input as soon a...

Page 12: ...ace interface of the control unit allows the connection to V2 optional modules Refer to V2 catalogue or to the technical sheets to see which optional modules with ADI interface are available for this...

Page 13: ...ENGLISH 39 PROGRAMMING WHEEL F1 10A...

Page 14: ...ial configuration menu accessible and explorable by means of the small wheel on the right side of the display allows programming the functions and times of the control unit WARNING Outside the configu...

Page 15: ...e correct position mCAUTION to perform the self learning procedure it is necessary to disable the ADI interface by means of the menu i Adi If some safeties are controlled by means of the ADI module th...

Page 16: ...operations are required for more then a minute the control unit exits from the programming mode without saving the given information and changes will be lost Keeping the wheel pushed downwards the con...

Page 17: ...in the closing phase In case there is an obstacle or the end of stroke operates the control unit can stop the opening phase before the relevant time expires To avoid that the gate does not close compl...

Page 18: ...ower is gradually increased until reached the set value or 100 if the take off is enabled Higher is the set value longer the length of time of the ramp that is the time necessary to reach the value of...

Page 19: ...e slowing down function in order to measure both opening and closing times and to enable it again once the setup has been carried out The control unit will automatically consider the working time dela...

Page 20: ...n with the opening phase command is ignored mWARNING a Start command in any phase of partial opening will cause the total opening the Start Pedestrian command is always ignored during a total opening...

Page 21: ...ng the opening cycle of the gate t LUC the relay is enabled at the receiving of a control of start or pedestrian start choosing this option a submenu is entered it allows to set the length of the acti...

Page 22: ...en as long as the Start input stays closed and it will close as long as Pedestrian Start stays closed oroL Timer operation the gate stays open while the Start input or Pedestrian Start input is closed...

Page 23: ...te starts moving Otherwise it will stand still and the flashing light will stay onfor 5 sec The whole test cycle lasts less than one second mWARNING V2 suggests to keep activated the test of the photo...

Page 24: ...m test enabled mWARNING V2 suggests to keep activated the test of the photocells in order to grant a higher safety of the system Encoder Input The PD18 control unit allows connection of the encoder in...

Page 25: ...is disabled the reverse manoeuvre lasts until the gate reaches the limit switch End of Programming This menu allows to finish the programming both default and personalized saving the modified data int...

Page 26: ...ou can alternate the display of thousands or units Area 2 is the reading of the number of cycles before the next request for service its value is rounded down to the hundreds Area 3 is the setup of th...

Page 27: ...ning it means that the setup cycle count down expired and the control unit shows that service is required OPERATION DEFECTS This paragraph shows some possible operation defects along with their cause...

Page 28: ...no Start command is not available ChiU Command close gate PAUS Stop the gate and goes in pause St Ch Start in closing StoP Stop Start command stop the gate APEr Start command open the gate St PA Star...

Page 29: ...en the gate is still no Not available Ch Photocell is active during the closing Ft tE no Si Test of operating of the photocells no CoS1 Input safety edge 1 fix edge no no Non active input AP Input act...

Reviews: