![V-TAC VT-66036103 Instruction Manual Download Page 32](http://html1.mh-extra.com/html/v-tac/vt-66036103/vt-66036103_instruction-manual_3108239032.webp)
29
5.5.7 RUN SETTING
5.5.7.1 RUN SETTING
Interface
Description
This interface is used to select run setting.
Press Up/Down button to move corresponding options;
Press Enter button to enter the selected menu.
Factory default Settings. Please consult the distributor for
modification.
RUN SETTING
1.REACT MODE
2.GRID POWER
3.DISC POWER
4.PV POWER
5.VAC-MIN
6.VAC-MAX
7.FAC-MIN
8.FAC-MAX
9.ACTIVE REP.
5.5.7.2 REACT MODE
Interface
Description
RUN SETTING
1.REACT MODE
2.GRID POWER
3.DISC POWER
REACT MODE
1.
POWER FACTOR
2.REACT POWER
3.QU WAVE
4.QP WAVE
POWER FACTOR
INPUT: C1.00
REACT POWER
INPUT: +00%
This interface is used to select react mode.
Press Up/Down button to move corresponding options;
Press Enter button to enter the selected menu.
QU WAVE (Reserved)
QP WAVE (Reserve
d
)
The input value should range between L0.80 and L0.99 or
C0.8 and C1.00.
The input value should range between -60% and
+60%, which varies with the standard.