AIR OPENINGS TO COMBUSTION AREA MUST NOT BE OBSTRUCTED. FOLLOW THE CHART
BELOW TO OBTAIN AND MAINTAIN ADEQUATE COMBUSTION AIR.
WarNiNG
1. When a boiler is located in an unconfined
space in a building of conventional construction
frame, masonry or metal, infiltration normally
is adequate to provide air for combustion and
ventilation.
However, in any building which
has been altered to conserve energy or to
minimize infiltration, the boiler area should
be considered as a coNFiNeD space.
If
there is any doubt, install air supply provisions
for combustion and ventilation in accordance
with section 5.3, Air for Combustion and Ventila-
VENTILATION & COMBUSTION AIR
comBUstioN air reQUirmeNts
(miNimUm opeNiNG iN sQUare iNcHes)
*
UNcoNFiNeD area
**
coNFiNeD area
oUtsiDe
comBUstioN air
iNsiDe
comBUstioN air
oUtsiDe
comBUstioN air
1 iN
2
/5000BtU
(paraGrapH 2)(sQ iN)
1 iN
2
/1000 BtU
(miN 100iN
2
) (FiG 4) (sQ iN)
1 iN
2
/4000 BtU
(FiG 3)(sQ iN)
1 iN
2
/2000 BtU
(FiG 3)(sQ iN)
BtU/Hr iNpUt
315,000
63
315
78.75
158
385,000
77
385
96.25
193
420,000
84
420
105
210
490,000
98
490
123
245
560,000
112
560
140
280
630,000
126
630
158
315
770,000
154
770
193
385
945,000
189
945
237
473
1,155,000
231
1155
289
578
1,540,000
308
1540
385
770
1,925,000
385
1925
482
963
2,310,000
462
2310
578
1155
2,695,000
539
2695
675
1348
3,080,000
616
3080
770
1540
* Unconfined area: A space whose volume is not less than 50 cubic feet per 1000 BTU per hour of all appliances in
-
stalled in that space (cubic feet of space = height x width x length).
** Confined area: A space whose volume is less than 50 cubic feet per 1000 BTU per hour of all appliances installed in
that space (cubic feet of space = height x width x length).
tion, of the latest revision of the NFPA 54 code,
the recommendations that follow, or applicable
provisions of the local building codes.
2. When a boiler is installed in an unconfined space,
in a building of unusually tight construction, air
for combustion and room ventilation must be
obtained from outdoors or from spaces freely
communicating with the outdoors. A permanent
opening or openings having a total free area
of not less than 1 square inch per 5,000 BTU
per hour of total input rating of all appliances