P/N 1070346 • REV 5.0 • ISS 03OCT11
7 / 32
Menu 8, Short Supervision Time
Short supervision is used to disable arming if the DGP does
not receive a supervision message from a sensor within the
short supervision time (20 minutes by default).
Menu 9, Long Supervision Time
Long supervision will set a fault condition in the panel for a
sensor/zone which supervision timer expired (2 hours by
default).
Program the supervision time to control how often the wireless
DGP checks the sensor is communicating and in range of the
wireless DGP.
Menu 10, Smoke Supervision Time
Menu 10 sets the supervision time for smoke sensors.
A smoke detector sends a supervisory signal every
63 minutes.
A Smoke supervision sets a fault condition in the panel when a
detector supervision timer expired (4 hours by default).
Program the supervision time to control how often the wireless
DGP checks that the sensor is communicating and in range of
the wireless DGP.
Menu 11, Supervision Options
The supervision function monitors sensors at the interval set
up in the previous procedure.
Long supervision and smoke supervision can be switched on
or off, or disabled by the first relay of the wireless DGP (relay
17 for DGP 1) to stop unwanted supervision failure messages.
The factory default for supervision is On.
Four-button fobs do not transmit a supervision signal; when
fobs are programmed, they automatically set supervision
to Off.
Menu 12, Receiver Sensitivity
Menu 12 is used to select the receiver sensitivity .
The sensitivity is also reduced by
−
6 dB in programming mode
by default. With this menu the sensitivity can be changed to
normal in programming mode.
After exit from the programming mode the sensitivity returns to
normal.
Menu 13, DGP Settings
The DGP can be configured for one of the following modes:
•
Extended 16 zones
•
Standard 13 + 3 zones
•
Extended 32 zones
•
Standard 29 + 3 zones
In the extended modes the DGP reports low battery, long or
smoke supervision, and smoke detector dirty state for each
sensor to the panel separately. This enables the panel to
handle this status information for each zone.
In the standard modes the first three zones of a DGP are
reserved to report supervision, low battery, and smoke detector
dirty state.
For example, on a DGP with address 1 the first three zones
are reserved as follows:
•
Zone 17, smoke sensors dirty. If any of the learned smoke
sensors reports a dirty state, this zone is in an alarm state.
•
Zone 18, supervision. If any of the learned zones is in
short supervision state then this zone alarms. If any of the
learned sensors is in long supervision or smoke
supervision state this zone is in tamper alarm state.
•
Zone 19, low battery. If any zone reports a low battery
fault, this zone is in an alarm state.
Menu 14, Factory Defaults
Menu 14 allows you to reset the wireless DGP to its factory
default settings (extended mode, 16 zones).
Caution:
Resetting clears the entire wireless DGP database.
Supported Sensors
•
TX-1011-03-1 Wireless Slimline door/window contact,
868 MHz GEN2, white
•
TX-1011-03-3 Wireless Slimline door/window contact,
868 MHz GEN2, brown
•
TX-1211-03-1 Universal Transmitter, 868 MHz GEN2,
white
•
TX-1211-03-3 Universal Transmitter, 868 MHz GEN2,
brown
•
TX-2211-03-1 Wireless PIR motion sensor, 868 MHz
GEN2
•
TX-2212-03-1 Mirror PIR, 868 MHz GEN2, Pet Immune
•
TX-2411-03-1 Wireless PIR/MW motion sensor, 868 MHz
GEN2
•
TX-6211-03-1 Wireless optical smoke/heat sensor,
868 MHz GEN2
•
TX-6212-03-1 Wireless optical smoke/heat sensor,
868 MHz GEN2
•
TX-4131-03-2 Wireless 4-button keyfob, 868 MHz GEN2
•
TX-3011-03-1 868 GEN2 2-button pendant panic, white
•
TX-5011-03-1 Shock sensor, 868 MHz GEN2, white
•
TX-5011-03-3 Shock sensor, 868 MHz GEN2, brown
Note:
The external contacts on TX-1011-03-1 and TX-1011-
03-3 are not supported in ATS1235 with firmware version 1.2
and earlier.
Specifications
Compatibility
Advisor Master: ATS1235 requires
Advisor Master control panel firmware
version V04.09.16 or later.
Advisor Advanced: ATS1235 requires
Advisor Advanced control panel firmware
version MR_017.017.0067 or later.
868 MHz AM (crystal and SAW) Learn
Mode wireless sensors.
Wireless zones
16 or 32 per DGP (programmable)
Fobs 16