important saFety notes

WarnIng

Do not open the camera assembly in a hazardous 
area when power is applied.  The device contains 
no  serviceable  components  and  should  not  be 
opened, except during installation and setup.  

CautIon

The wiring procedures in this manual are intended 
to  ensure  proper  functioning  of  the  device  under 
normal  conditions.    However,  because  of  the 
many  variations  in  wiring  codes  and  regulations, 
total  compliance  to  these  ordinances  cannot  be 
guaranteed.    Be  certain  that  all  wiring  complies 
with  the  NEC  as  well  as  all  local  ordinances.    If 
in  doubt,  consult  the  authority  having  jurisdiction 
before wiring the system.  

attentIon

Observe  precautions  for  handling  electrostatic 
sensitive devices.  Do not plug the camera module 
into the base with power applied.

installation

CautIon

Installation  and  wiring  of  the  xWatch  should  be 
performed only by qualified personnel.

ProtECtIon AgAInst MoIsturE DAMAgE

It is important to take proper precautions during installation 

to ensure that moisture will not come in contact with the 

electrical connections or components of the system.  The 

integrity  of  the  system  regarding  moisture  protection 

must  be  maintained  for  proper  operation  and  is  the 

responsibility of the installer.

If  conduit  is  used,  drains  must  be  installed  at  water 

collection  points  to  automatically  drain  accumulated 

moisture.  Conduit breathers should be installed at upper 

locations to provide ventilation and allow water vapor to 

escape.  At least one breather should be used with each 

drain.

Conduit  raceways  should  be  inclined  so  that  water  will 

flow to low points for drainage and will not collect inside 

enclosures  or  on  conduit  seals.    If  this  is  not  possible, 

install  conduit  drains  above  the  seals  to  prevent  the 

collection of water or install a drain loop below the camera 

with a conduit drain at the lowest point of the loop.

Conduit  seals  are  not  required  for  compliance  with 

explosion-proof installation requirements, but are highly 

recommended  to  prevent  water  ingress  in  outdoor 

applications.    Units  with  M25  thread  must  use  an  IP66 

washer to prevent water ingress.

Summary of Contents for Det-Tronics xWatch X7050

Page 1: ...Instructions 95 8600 xWatch Explosion Proof Camera X7050 2 1 6 09 95 8600 ...

Page 2: ...age 4 Camera Location 5 Camera Mounting 5 Wire Size and Type 5 Wiring Procedure 6 Aiming the Camera 7 Leveling the Camera 7 Converting a C7050 Flame Detector to X7050 xWatch 8 Troubleshooting 9 Replacing the xWatch Camera Module 9 Maintenance 9 Cleaning 9 O Rings 9 Device Repair And Return 10 Ordering Information 10 Accessories 10 Replacement Parts 10 Assistance 10 ...

Page 3: ...ube module in an existing C7050 Flame Detector to provide basic visual information xWatch can be ordered from the factory as a combined unit with any X Series flame detector With this arrangement the camera and detector share the same field of view In the event of a fire or gas alarm the operator can immediatelyviewthemonitoredareatodeterminewhether personnel are present and safe An accurate evalu...

Page 4: ...ing 22 AWG to 16 AWG twisted pair cable of 100 ohm impedance The monitor end must terminate the video cable with 100 ohms Since most monitors have a built in termination resistor of 75 ohms instead of 100 ohms a balun or other matching network video converter must be used A variety of matrix control systems or DVRs can be suitable for viewing or recording the video signal depending on the requirem...

Page 5: ... 2 G Ex d IIC T5 IP66 FM07ATEX0053 Ta 40 C to 75 C IECEx Certificate of Conformity IECEx FMG 07 0019 Ex d IIC T5 IP66 Ta 40 C to 75 C User Interface Conventional off the shelf video switchers and controllers can be used for the interface Housing Material Aluminum or 316 Stainless Steel Shipping Weight Approximate Aluminum 1 2 pounds 0 6 kg Stainless Steel 2 2 pounds 1 0 kg Dimensions See Figures 2...

Page 6: ...roperprecautionsduringinstallation to ensure that moisture will not come in contact with the electrical connections or components of the system The integrity of the system regarding moisture protection must be maintained for proper operation and is the responsibility of the installer If conduit is used drains must be installed at water collection points to automatically drain accumulated moisture ...

Page 7: ...Because composite video frequencies span the range of 25 Hz to 6 MHz most cables will display transmission line characteristics Ensure that the same cable type impedance is used throughout the entire length For example do not mix twisted pair cable and coaxial cable without using a balun for matching In addition the monitor end must be properly terminated Failure to properly implement the video ca...

Page 8: ...ring connected to the xWatch with a meg ohmmeter Disconnect wiring at the camera before checking system wiring for continuity Check all field wiring to be sure that the proper 4 connections have been made Using the index pin as a guide install the camera 5 module on the terminal block Re assemble the device housing 6 Make the final sighting adjustments and ensure that 7 the mounting bracket hardwa...

Page 9: ...a s field of view to match the center of the detector s field of view The COV tester can also be used to locate the outside edge of the field of view Leveling the Camera If the image on the monitor does not appear to be level this can be corrected by rotating the camera module within the xWatch Remove the housing cover from the xWatch See 1 Figure 5 Loosen the setscrew on the side of the xWatch 2 ...

Page 10: ...ector Disconnect the existing wiring at the controller 4 Connect the grounding strap between the new index pin and the terminal mounting screw per the instructions See Figure 9 Important Do not test any wiring connected to the xWatch with a meg ohmmeter Disconnect wiring at the camera before checking system wiring for continuity Check all field wiring to be sure that the proper 5 connections have ...

Page 11: ...s Clean the camera lens using a clean cloth or tissue and Det Tronics window cleaning solution part number 001680 001 If a stronger solution is needed isopropyl alcohol may be used O Rings Rubber O rings are used on the xWatch housing to ensure the watertight integrity of the device It is imperative that these O rings be properly installed and in good condition Failure to properly maintain these r...

Page 12: ...ng Bracket p n 004404 002 Q1201A Laser Holder Laser is used for sighting the flame detector and xWatch camera The Laser Holder easily attaches to the front of the detector or camera The Laser projects a red laser beam to show the exact center of the field of view Additional laser positions are provided to show the outside edges of the field of view Replacement Parts Part Number Description 009448 ...

Page 13: ...ch Eclipse IR Combustible Gas Detector Eagle Quantum Premier Safety System Eagle Logic Solver Safety System Det Tronics the DET TRONICS logo and xWatch are registered trademarks or trademarks of Detector Electronics Corporation in the United States other countries or both Other company product or service names may be trademarks or service marks of others Copyright Detector Electronics Corporation ...

Reviews: