background image

2.1

95-8600

10

Device repair anD return

Prior  to  returning  devices,  contact  the  nearest  local 

Detector  Electronics  office  so  that  a  Return  Material 

Identification (RMI) number can be assigned.  A written 

statement  describing  the  malfunction  must  accompany 

the returned device or component to assist and expedite 

finding the root cause of the failure.

Pack  the  unit  properly.    Always  use  sufficient  packing 

material.    Where  applicable,  use  an  antistatic  bag  as 

protection from electrostatic discharge.

NOTE

Inadequate  packaging  that  ultimately  causes 
damage  to  the  returned  device  during  shipment 
will result in a service charge to repair the damage 
incurred during shipment.

Return all equipment transportation prepaid to the factory 

in Minneapolis.

orDerinG inFormation

When ordering, please specify:
x7050 xWatch explosion proof camera
Refer to the xWatch Model Matrix below for details.

ACCEssorIEs
swivel  Mount  Bracket

  is  required  for  mounting  the 

camera:

Q9001B1175 

Aluminum 

Mounting 

Bracket  

 

  (p/n 002099-003)
Q9001H8001  Stainless  Steel  Mounting  Bracket 

 

  (p/n 004404-002)

Q1201A  laser  holder/laser

  is  used  for  sighting  the 

flame  detector  and  xWatch  camera.    The  Laser  Holder 

easily  attaches  to  the  front  of  the  detector  or  camera.  

The Laser projects a red laser beam to show the exact 

center of the field of view.  Additional laser positions are 

provided to show the outside edges of the field of view.

rEPlACEMEnt PArts
Part number  Description

009448-003 

Model DE2020N –  

 

Replacement Camera Module, NTSC

009448-004 

Model DE2020P –  

 

Replacement Camera Module, PAL

107427-004 

Rubber O-rings

001680-001 

Window cleaner squeeze bottle  

 

(package of six bottles)

005003-001  

Silicone-free grease

AssIstAnCE

For assistance in ordering a system to meet the needs of 

a specific application, contact:

Detector Electronics Corporation

6901 West 110th Street

Minneapolis, Minnesota  55438  USA

Operator:  (952) 941-5665 or (800) 765-FIRE

Customer Service:  (952) 946-6491

Fax:  (952) 829-8750

Web site:  www.det-tronics.com

E-mail:  [email protected]

xWAtCh MoDEl MAtrIx

MoDEl

DEsCrIPtIon

x7050

xWatch Explosion Proof Camera

tyPE

MAtErIAl

A

Aluminum

B

Stainless Steel (316)

tyPE

thrEAD tyPE

1E

1/2’ NPT

1F

M20

tyPE

VIDEo outPut

50

NTSC

51

PAL

tyPE

APProVAl AgEnCy

W

FM/CSA/ATEX/CE

tyPE

ClAssIFICAtIon

2

Division/Zone Ex d 

Summary of Contents for Det-Tronics xWatch X7050

Page 1: ...Instructions 95 8600 xWatch Explosion Proof Camera X7050 2 1 6 09 95 8600 ...

Page 2: ...age 4 Camera Location 5 Camera Mounting 5 Wire Size and Type 5 Wiring Procedure 6 Aiming the Camera 7 Leveling the Camera 7 Converting a C7050 Flame Detector to X7050 xWatch 8 Troubleshooting 9 Replacing the xWatch Camera Module 9 Maintenance 9 Cleaning 9 O Rings 9 Device Repair And Return 10 Ordering Information 10 Accessories 10 Replacement Parts 10 Assistance 10 ...

Page 3: ...ube module in an existing C7050 Flame Detector to provide basic visual information xWatch can be ordered from the factory as a combined unit with any X Series flame detector With this arrangement the camera and detector share the same field of view In the event of a fire or gas alarm the operator can immediatelyviewthemonitoredareatodeterminewhether personnel are present and safe An accurate evalu...

Page 4: ...ing 22 AWG to 16 AWG twisted pair cable of 100 ohm impedance The monitor end must terminate the video cable with 100 ohms Since most monitors have a built in termination resistor of 75 ohms instead of 100 ohms a balun or other matching network video converter must be used A variety of matrix control systems or DVRs can be suitable for viewing or recording the video signal depending on the requirem...

Page 5: ... 2 G Ex d IIC T5 IP66 FM07ATEX0053 Ta 40 C to 75 C IECEx Certificate of Conformity IECEx FMG 07 0019 Ex d IIC T5 IP66 Ta 40 C to 75 C User Interface Conventional off the shelf video switchers and controllers can be used for the interface Housing Material Aluminum or 316 Stainless Steel Shipping Weight Approximate Aluminum 1 2 pounds 0 6 kg Stainless Steel 2 2 pounds 1 0 kg Dimensions See Figures 2...

Page 6: ...roperprecautionsduringinstallation to ensure that moisture will not come in contact with the electrical connections or components of the system The integrity of the system regarding moisture protection must be maintained for proper operation and is the responsibility of the installer If conduit is used drains must be installed at water collection points to automatically drain accumulated moisture ...

Page 7: ...Because composite video frequencies span the range of 25 Hz to 6 MHz most cables will display transmission line characteristics Ensure that the same cable type impedance is used throughout the entire length For example do not mix twisted pair cable and coaxial cable without using a balun for matching In addition the monitor end must be properly terminated Failure to properly implement the video ca...

Page 8: ...ring connected to the xWatch with a meg ohmmeter Disconnect wiring at the camera before checking system wiring for continuity Check all field wiring to be sure that the proper 4 connections have been made Using the index pin as a guide install the camera 5 module on the terminal block Re assemble the device housing 6 Make the final sighting adjustments and ensure that 7 the mounting bracket hardwa...

Page 9: ...a s field of view to match the center of the detector s field of view The COV tester can also be used to locate the outside edge of the field of view Leveling the Camera If the image on the monitor does not appear to be level this can be corrected by rotating the camera module within the xWatch Remove the housing cover from the xWatch See 1 Figure 5 Loosen the setscrew on the side of the xWatch 2 ...

Page 10: ...ector Disconnect the existing wiring at the controller 4 Connect the grounding strap between the new index pin and the terminal mounting screw per the instructions See Figure 9 Important Do not test any wiring connected to the xWatch with a meg ohmmeter Disconnect wiring at the camera before checking system wiring for continuity Check all field wiring to be sure that the proper 5 connections have ...

Page 11: ...s Clean the camera lens using a clean cloth or tissue and Det Tronics window cleaning solution part number 001680 001 If a stronger solution is needed isopropyl alcohol may be used O Rings Rubber O rings are used on the xWatch housing to ensure the watertight integrity of the device It is imperative that these O rings be properly installed and in good condition Failure to properly maintain these r...

Page 12: ...ng Bracket p n 004404 002 Q1201A Laser Holder Laser is used for sighting the flame detector and xWatch camera The Laser Holder easily attaches to the front of the detector or camera The Laser projects a red laser beam to show the exact center of the field of view Additional laser positions are provided to show the outside edges of the field of view Replacement Parts Part Number Description 009448 ...

Page 13: ...ch Eclipse IR Combustible Gas Detector Eagle Quantum Premier Safety System Eagle Logic Solver Safety System Det Tronics the DET TRONICS logo and xWatch are registered trademarks or trademarks of Detector Electronics Corporation in the United States other countries or both Other company product or service names may be trademarks or service marks of others Copyright Detector Electronics Corporation ...

Reviews: