-6-
G
VENT TERMINATION CLEARANCES
A.
Minimum 4-foot (1.22m) clearance below or beside any door or window that opens.
B.
Minimum 1-foot (0.3m) clearance above any door or window that opens.
C.
Minimum 3-foot (0.91m) clearance from any adjacent building.
D.
Minimum 7-foot (2.13m) clearance from any grade when adjacent to public walkways.
E.
Minimum 2-foot (0.61m) clearance above any grass, plants, or other combustible materials.
F.
Minimum 3-foot (0.91m) clearance from an forced air intake of any appliance.
G.
Minimum 2-foot (0.61m) clearance below eves or overhang.
H.
Minimum 1-foot (0.3m) clearance horizontally from combustible wall.
I.
Must be a minimum of 3 foot (0.91m) above the roof and 2 foot (0.61m) above the highest point or the roof
within 10 feet (3.05m).
FIGURE 6
VENT TERMINATION CLEARANCES
PELLET VENT TYPE
A UL listed 3-inch or 4-inch type “PL” pellet vent exhaust system must be used for installation and attached to the
pipe connector provided on the back of the stove (use a 3-inch to 4-inch adapter for 4-inch pipe). Connection
at back of stove must be sealed using Hi-Temp RTV. Use 4-inch vent if the vent height is over 12-feet or if the
installation is over 2,500 feet above sea level. We recommend the use of Simpson Dura-Vent® or Metal-Fab®
pipe (if you use other pipe, consult your local building codes and/or building inspectors). Do not use Type-B
Gas Vent pipe or galvanized pipe with this unit. The pellet vent pipe is designed to disassemble for cleaning and
should be checked several times during the burning season. Pellet vent pipe is not furnished with the unit and
must be purchased separately.
PELLET VENT INSTALLATION
The installation must include a clean-out tee to enable collection of fly ash and to permit periodic cleaning
of the exhaust system. 90-degree elbows accumulate fly ash and soot, thereby reducing exhaust flow and
performance of the stove. Each elbow or tee reduces draft potential by 30% to 50%.
All joints in the vent system must be fastened by at least 3 screws, and all joints must be sealed with Hi-Temp
RTV silicone sealant to be airtight. The area where the vent pipe penetrates to the exterior of the home must
be sealed with silicone or other means to maintain the vapor barrier between the exterior and the interior of the
home. Vent surfaces can get hot enough to cause burns if touched. Noncombustible shielding or guards may
be required.
PELLET VENT TERMINATION
Do not terminate the vent in an enclosed or semi-enclosed area, such as. carport, garage, attic, crawl space,
under a sundeck or porch, narrow walkway, or any other location that can build up a concentration of fumes.
Termination in one of these areas can also lead to unpredictable pressure situations with the appliance; and
could result in improper performance and/or malfunction.
The termination must exhaust above the outside air inlet elevation.
The termination must not be located where it will become plugged by snow or other materials.
Do not terminate the venting into an existing steel or masonry chimney.