4.5.1 I/O
4.5.1.1 DI
This section explains how to configure monitoring condition on digital input, and take certain
actions once the condition is reached.
Figure 4-5-1-1
DI
Item
Description
Enable
Enable or disable DI.
Mode
Options are "High Level", "Low Level", and "Counter".
Duration (ms)
Set the duration of high/low level in digital input. Range: 1-10000.
Condition
Select from "Low->High", and "High-> Low".
Low->High
The counter value will increase by 1 if digital input's status changes from low level to
high level.
High->Low
The counter value will increase by 1 if digital input's status changes from high level to
low level.
Counter
The system will take actions accordingly when the counter value reach the preset
one, and then reset the counter value to 0. Range: 1-100.
Action
Select the corresponding actions that the system will take when digital input mode
meets the preset condition or duration.
SMS
Check to enable SMS alarm.
Phone
Set phone number to receive SMS alarm.
Content
Set the content of SMS alarm.
Check to enable Email alarm.
DO1
Control output status of DO1.
DO2
Control output status of DO2.
Cellular UP
Trigger the gateway to switch from offline mode to cellular network mode.
Table 4-5-1-1 DI Parameters