18

value.

NOTE: The Meter is designed for 
measurement in single - phase systems. It 
is possible to measure in a three - phase 
system by creating an artificial neutral 
point by using a three phase adapter.

4.6 Measuring power factor

 WARNING: 

MAXIMUM INPUT 

VOLTAGE OF AC VOLT RANGE IS 750V 
RMS. DO NOT ATTEMPT TO MEASURE 
ANY VOLTAGE THAT EXCEEDS 750V RMS 
TO AVOID ELECTRICAL SHOCK HAZARD 
OR DAMAGE TO THE INSTRUMENT.

1. Put the Meter in the COS   range.
2. Connect the black and red test 
leads to the COM and V terminals 
respectively.
3. Clamp the jaws around the current 
carrying conductor ensuring a good 
contact between the closing faces of 
the jaws.
4. Apply the test leads to the circuit 
under test. (See figure 4.5).
5. Read the displayed value.
A time lag / lead power factor is 
indicated on the display by – and + 
signs (of the upper part ) as well as 
by “Ind” and “Cap” letters (of the 
lower part).

4.7 Measuring AC Voltage

1. Put the Meter in the V range.
2. Connect the black and red test 
leads to the COM and V terminals 
respectively.
3. Apply the test leads to the circuit 
under test.
4. Read the displayed voltage.

4.8 Measuring AC Current

 CAUTION:

 MAXIMUM INPUT CURRENT 

IS 700A RMS. BEFORE SELECTING THE 
CURRENT MEA-SUREMENT FUNCTION 

ENSURE THAT THE TEST LEADS ARE 
DISCONNECTED FROM THE INSTRUMENT.

1. Put the Meter in the A range.
2. Clamp the jaws around the current 
carrying conductor, ensuring a good 
contact between the closing faces of 
the jaws.
3. Read the measured current.

4.9 Integrating Energy

 WARNING:

 MAXIMUM INPUT 

VOLTAGE OF AC VOLT RANGE IS 750V 
RMS. DO NOT ATTEMPT TO MEASURE 
ANY VOLTAGE THAT EXCEEDS 750V RMS 
TO AVOID ELECTRICAL SHOCK HAZARD 
OR DAMAGE TO THE INSTRUMENT.

1. When the ENERGY pushbutton has 
been pressed, the Meter defaults in 
the true energy integrating mode 
and time stamping mode (ENERGY, 
KW.h,: and AUTO displayed).
2. Connect the black and red test 
leads to the COM and V terminals 
respectively.
3. Clamp the jaws around the current 
carrying conductor under test, 
ensuring a good contact between the 
closing faces of the jaws.
4. Apply the test leads to the circuit 
under test and press the ENERGY 
button to scroll through the true, 
apparent, and reactive energy value. 
The elapsed time between the last 
value and the start of the integration 
is shown in the upper display.
5. Press and hold the ENERGY button 
for two seconds to exit Energy 
Integrating mode. See 3.2 Operating 
State Diagram for more information.

5. MAINTENANCE AND 

CALIBRATION

5.1 Battery Replacement

Summary of Contents for UD370

Page 1: ...Lea entienda y siga las instrucciones de seguridad contenidas en este documento antes de operar esta herramienta WARNING Read understand and follow the safety rules in this document before operating t...

Page 2: ...5 MANTENIMIENTO Y CALIBRACI N 8 5 1 Reemplazo de la bater a 5 2 Mantenimiento 5 3 Calibraci n 6 MEDICIONES DE POTENCIA TRIF SICA 9 7 ADAPTADOR 3 FASES OPCIONAL 9 8 ESPECIFICACIONES T CNICAS 10 8 1 Es...

Page 3: ...strados en las especificaciones el ctricas Nunca mida corrientes mientras las puntas de prueba se encuentren insertas en los conectores de entrada Nunca use el medidor o las puntas de prueba cuya prot...

Page 4: ...8 V Terminal de entrada para medici n de voltaje 9 KVAR Selecciona el modo de medici n de Potencia Reactiva 10 COM Terminal com n neutro 11 KW Selecciona el modo de medici n de Potencia Real 12 KVA Se...

Page 5: ...integrador de energ a est activado 24 Indicadores de unidades de medici n Estos s mbolos indican las unidades de medici n de cada lectura en cualquier funci n 25 ENERGY Mostrado en pantalla cuando el...

Page 6: ...R FORMA DA ADAS O DEGRADADAS NO LAS USE DEBER N SER REEMPLAZADAS 4 4 Auto prueba Encendido Presione y sostenga el bot n ON OFF para encender el medidor e iniciar la auto prueba El medidor emite un ton...

Page 7: ...s quijadas del gancho alrededor del conductor de corriente a ser probado Aseg rese de que exista buen contacto en las caras de contacto de las quijadas 4 Aplique las puntas de prueba al circuito a ser...

Page 8: ...el uso de la bater a alcalina especificada u otras bater as de larga duraci n Si el indicador low battery es mostrado en pantalla reemplace la bater a usando los siguientes procedimientos ADVERTENCIA...

Page 9: ...anualmente Respecto al servicio o informaci n sobre la calibraci n contacte a su distribuidor m s cercano 6 MEDICIONES DE POTENCIA TRIF SICA Refi rase a las siguientes figuras para las maneras sugeri...

Page 10: ...la medici n en un sistema desbalanceado 3 fases 3 hilos Repita las conexiones mostradas en las figuras anteriores y acumule los valores mostrados en pantalla para obtener la medici n de potencia trif...

Page 11: ...cional no sinusoidal Factor de cresta 1 3 3 5 Error de lectura 0 5 3 Para la forma de onda continua de 45 Hz a 65 Hz menor a 1000A pico Medici n de Volts CA Rango Resoluci n 400 V 750 V 0 1 V 1 V Pres...

Page 12: ...a 450 Hz 8 3 Especificaciones generales Pantalla LCD de 4 d gitos para potencia LCD de 6 d gitos para energ a Velocidad de conversi n A D aprox 4 veces seg para digital M ximo voltaje a Tierra 600V RM...

Page 13: ...ntegrating Energy 5 MAINTENANCE AND CALIBRATION 18 5 1 Battery Replacement 5 2 Maintenance 5 3 Calibration 6 THREE PHASE POWER MEASUREMENTS 19 7 THREE PHASE ADAPTOR OPTIONAL 20 8 TECHNICAL SPECIFICATI...

Page 14: ...her than the maximum limits of the input values shown in the electrical specifications Never measure any current while the test leads are inserted into the input jacks Never use the Meter or test lead...

Page 15: ...reactive power measurement mode 10 COM Common Terminal 11 kW Selects true power measurement mode 12 kVA Selects apparent power measurement mode 13 MIN MAX Selects MAX MIN recording mode and displays r...

Page 16: ...isplayed when ENERGY pushbutton has been pressed 26 Automatically indicate negative digital displays in the power factor COS measurement mode 27 AUTO Displayed when the auto ranging mode is active 28...

Page 17: ...battery before using the Meter when the low battery indicator is displayed on the LCD If the Meter does not turn ON the battery is missing or worn out To replace the battery see 5 1 Battery Replacemen...

Page 18: ...MAXIMUM INPUT CURRENT IS 700A RMS BEFORE SELECTING THE CURRENT MEA SUREMENT FUNCTION ENSURE THAT THE TEST LEADS ARE DISCONNECTED FROM THE INSTRUMENT 1 Put the Meter in the A range 2 Clamp the jaws ar...

Page 19: ...e battery cover Then insert the battery into position Dress the battery leads so that they will not be pinched between the case bottom and the case top Do not discard battery cover 6 Replace the rear...

Page 20: ...r Unbalanced 3 phase 3 wire system Measurement Connections in a Balanced 3 phase 3 wire system 1 Set the Model 370 at kW or kVA or Cos range position 2 Hook on the 3 phase adaptor to the input jacks o...

Page 21: ...n The accuracy is specified from 5 to 100 of the selected range True Power Measurement Range Resolution 400 Kw 750 Kw 0 1 kW 1 Kw Accuracy 1 5 2 Frequency 45 Hz to 450 Hz Overload 750V RMS 1000A PEAK...

Page 22: ...eading 0 5 3 For the continuous waveform of 45 Hz to 65 Hz less than 750V RMS True Power Energy Integrator Range Resolution 40000 kWh 75000 kWh 0 1 kWh 1 kWh Accuracy 1 5 2 Frequency 45 Hz to 450 Hz M...

Page 23: ...ow Battery Indication The is displayed when the battery voltage drops below the operating voltage Battery Life 80hours typical alkaline Battery Type NEDA 1604A 9V or 6LF22 9V Maximum Conductor Size 51...

Page 24: ...s casos a Cuando la herramienta se haya utilizado en condiciones distintas a las normales b Cuando el producto hubiera sido alterado de su composici n original o reparado por personas no autorizadas p...

Reviews: