DS1067-063D
109
LBT20064
MESSAGE
FAILURE MEMORY
MESSAGE
DIAGNOSE LOG.
CAUSE
FINDING AND RESOLVING THE PROBLEM
PSTN FAILURE
CONTROL PANEL
FAILURE STARTS
UC00.CTRL PANEL
PSTN FAILURE
Failure on the PSTN
telephone line: the call
tone was not detected
for 3 consecutive line
tests,
during
the
automatic line control or
when trying to send a
message.
Note
:
The line test,
if enabled,
is carried out every 15
minutes.
The ATS4 test,
if
enabled, is carried out
continually.
Check if the PSTN line was mistakenly enabled when
not in use.
Check the connection of the telephone line on the "LINE"
input terminals.
Check the efficiency of the telephone line.
Check if there is a telephone device connected
upstream, between the control panel and the telephone
line (in case of connection of a PABX switchboard,
exclude the line test).
GSM FAILURE
CONTROL PANEL
FAILURE STARTS
UC00.CTRL PANEL
GSM FAILURE
Failure on the GSM
channel
caused
by:
prolonged absence of
the GSM field, absence
of
the
SIM
card,
incorrect PIN of the SIM
card or there is no
credit on the SIM card.
Check if the GSM line was mistakenly enabled in
absence of the GSM module.
Check the correct assembly of the GSM antenna and
correct fitting of the SMA connector.
Check the presence and intensity of the GSM field via a
test (try installing a remote 1067/014 antenna).
Check for the presence and the correct positioning of the
SIM card (delete any potential contacts).
Check if the SIM card has the PIN enabled and, if so,
that it was programmed correctly in the control panel.
Check the remaining credit on the SIM card.
ANOM. BUS
TSnn.TS xx
FAILURE STARTS BUS
TSnn.TS xx
FAILURE BUS
CONNECTION
The bus device
signalled is not
communicating
(keypad, reader key,
expansion), that control
panel has not been
answered.
Check the cabling of the device/s at the bus
(disconnected wires or short circuits or inverted polarity.
Check the bus power supply.
ANOM. BUS
LTnn.LT xx
FAILURE STARTS BUS
LTnn.LT xx
FAILURE
BUS
CONNECTION
ANOM. BUS
Ernn.ER xx
FAILURE STARTS BUS
Ernn.ER xx
FAILURE
BUS
CONNECTION
ANOM. BUS
ASnn.AS xx
FAILURE STARTS BUS
ASnn.AS xx
FAILURE
BUS
CONNECTION
ANOM. BUS
EWnn.EW xx
FAILURE STARTS BUS
EWnn.EW xx
FAILURE
BUS
CONNECTION
FAILURE STARTS
POWER INSTANT
CONTROL PANEL
LACK OF POWER
Instantaneous absence
of mains power supply
in control panel (power
supply voltage < 9 V for
at least 3 seconds).
Check the presence and the connection of the mains
power supply.
Check the quality of the connection between the power
supply and the control panel (+PS and -PS).
FAILURE STARTS
POWER INSTANT
ASnn.AS xx
LACK OF POWER
Instantaneous absence
of mains power supply
in supplementary power
supply ASnn (power
supply voltage < 9 V for
at least 3 seconds).
Check the presence and the connection of the mains
power supply.
Check the quality of the connection between the power
supply and the ASnn (+PS and -PS).
FAILURE STARTS
NETWORK
SYSTEM
LACK OF POWER
Prolonged absence of
mains power supply
(power supply voltage
< 9 V for a time longer
than “lack of power
time”)
Check the presence and the connection of the mains
power supply.
Check the quality of the connection between the power
supply and the control panel or AS (+PS and -PS).
LOW BATTERY
CONTROL PANEL
FAILURE STARTS BATT.
CONTROL PANEL
BATTERY LOW
Battery voltage < 2 V.
Check the battery connection
Replace the battery.
Battery
voltage
< 12.5 V during test.
If the problem persists for a few days, replace the battery.
During a lack of power,
the voltage of the battery
went below 11.5 V (flat
battery).
If after the mains power supply is restored the problem
persists for a few days, replace the battery.