4.3 Operation settings
The operation settings and alarm
acknowledgements are carried out
in the soft ware menu.
The menu is opened by pressing
the Enter key (
) at any stage in
the soft ware. The arrow keys
(
and
) are used to navigate
in the menu. The desired operation
setting may also be selected using
the shortcut number key. The table
below presents the shortcut keys.
The desired setting is selected
using the Enter key. The setting is
changed by pressing the arrow keys
and accepted using the Enter key.
The number key 9 exits the menu.
OPERATION SETTING MENUS:
Change the setting with the arrow keys (
and
) and accept by pressing Enter
(
). The number key 9 exits the menu.
Menu
Fin -> Swe/Eng 0
Fin -> Swe / Eng
Suomi
Language selection
Move to language selection by pressing Enter. Change language by pressing the arrow keys
and accept by pressing Enter.
Menu
Sludge bag 1
Sludge bag
Yes
Sludge emptying method selection
In the treatment plant, sludge is removed by default using a sludge bag.
If you want to remove sludge using a vacuum truck, move to the selection by pressing Enter,
change the default setting with the arrow buttons (No) and confi rm the selection by pressing
Enter.
The sludge pump does not transfer sludge into the sludge bag. The sludge removal reminder
is given automatically aft er 6 months.
The sludge counter resets when you acknowledge the reminder.
If you remove sludge using a vacuum truck before the sludge removal reminder, reset the
sludge counter by pressing the
button.
Menu
Sludge alarm 2
Sludge bag alarm
No
Sludge bag replacement reminder every 3 months (not on by default).
The function is activated by choosing Yes and pressing Enter.
If you change the sludge bag before the sludge removal reminder, reset the sludge counter
by pressing the
button.
Menu
Process block 3
Process block
16.00
No
Specifying sampling time
The function is activated by choosing Yes and pressing Enter. Feed the process block end
time in numbers and press Enter. The time is specifi ed by being 7 h 30 min before the samp-
ling time. Sampling will not succeed, however, if the process has not started due to low load.
Menu
Alarms 4
Reset
No
Alarm acknowledgement
If there are several alarms, you can use the
key to browse the alarm screens.
Menu
Night alarm 5
Night alarm
No
Sending alarm messages (GSM modem) between 22.00 and 07.00. When night alarm is not
in use, the alarm SMS will be sent at 07.01 (not on by default)
Menu
Time settings 6
Time setting
11.01. 16.06
Date and time
Input the correct time with the number keys. The number is input in sequences of four digits.
Pressing Enter moves to the next sequence.
Menu
Alarm GSM number
7
Alarm GSM number
+35840123456
The mobile phone number where the alarm message
(GSM modem) is sent
Enter the number starting with the country code (F358) and leave out the fi rst 0
in the GSM number. Aft er each sequence of four numbers, press Enter. If the length of the
number diff ers from setting (default: Finland), acknowledge the last fi eld of 4 digits by
leaving 0 as the fi nal digit. Remove the extra fi nal number by pressing the
key.
Re-enter the 3 fi nal digits and acknowledge.
Menu
IO-test 8
Test In 0000
Out 000000
Testing of active level switch and equipment
When the device or switch is active, the zero is replaced by a 1. During IO testing, the
process is stopped.
In 0000 active level switches in order: From left
Storage tank level switch
Process tank level switch
Chemical tank level switch
Overfl ow pipe level switch
Out 000000 running equipment in order:
Test number key
Transfer pump
0
Emptying pump
1
Chemical pump
2
Compressor
3
Sludge pump
4
Lamp
5
To test the functionality of a device, press the corresponding number key. If you press the
button, the chemical pump runs for 60 sec. while the signal lamp fl ashes.
Menu
Exit 9
The number key 9 or Enter exits the menu.
16