System menu
The System menu provides settings on how to configure and operate the mechanical
equipment.
Field
Range
Access Description
Set to
PWM, BOIL,
ELEC,
Default =
PWM
Installer
APPLICATION MODE
— Select the control
application mode.
PWM = Hydronic pulse width modulation
BOIL = Hydronic boiler heats snow melting system
ELEC = Electric snow melt
NONE, 090,
095
Default =
090
Installer
SNOW/ICE SENSOR
— Selects if a Pavement
Snow and Ice Sensor or Aerial Snow Sensor is
installed.
OFF or ON
Default =
ON
Installer
SLAB SENSOR
— Selects if a Slab Sensor for
Aerial Snow Sensor is installed to measure the
slab temperature.
Conditions:
Application Mode is set to PWM,
Boil or Elec and Snow/Ice Sensor is set to None
or 095.
OFF or ON
Default =
ON
Installer
SLAB PROTECTION
— Select if the slab should
be protected from large temperature differentials
to avoid cracking the concrete due to high tensile
stress.
Conditions:
Application Mode is set to Boil and
Snow/Ice Sensor is set to 090 or Slab Sensor is
set to On.
OFF or ON
Default =
OFF
Installer
ECONOMELT
— EconoMelt allows the user to
mechanically remove snow then manually start
the system to melt the thin snow layer or ice.
Conditions:
Application Mode is set to PWM,
Boil or Elec.
SYS
(System
Pump)
or ALRT
(Alert)
Default =
SYS
Installer
AUXILIARY RELAY
— Select if the auxiliary
relay should function as system pump or as
an alert.
Conditions:
Application Mode is set to PWM
or Boil.
0.5 to 7.0
days, OFF
Default = 3.0
days
Installer
MAXIMUM MELT TIME
— Select to limit
the amount of melting run time after snow is
automatically detected by the Pavement Snow
and Ice Sensor or Aerial Snow Sensor.
Conditions:
Application Mode is set to PWM,
Boil or Elec.