14 | uponorpro.com
Access levels and access
level lock
The control is shipped pre-programmed
with common settings. The control has an
Installer access level that allows full access
to all settings and a user access level that
restricts the number of settings available.
The control defaults to the User access
level after 12 hours of operation.
To change to the Installer access level:
• In the Toolbox menu, locate Access.
• Adjust the access level to Installer by
pressing the up or down button. This will
permit setting changes to the control.
View menu (1 of 2)
The View menu displays the current operating temperatures and status information
of the system.
Field
Range
Access Description
Set to
– – –,
-76 to 149ºF
(-60 to 65ºC)
User
Installer
OUTDOOR
— Current outdoor air temperature
as measured by the local outdoor sensor.
Conditions:
Application Mode is set to PWM,
Boil or Elec.
– – –,
-76 to 149ºF
(-60 to 65ºC)
Installer
SLAB TARGET
— This field displays the
calculated slab target of the snow melting
system. Three dashes (– – –) display when
the snow melt control is off.
Conditions:
Application Mode is set to PWM,
Boil or Elec and a snow/ice sensor or slab
sensor is installed.
-76 to 149ºF
(-60 to 65ºC)
User
Installer
SLAB
— Current slab temperature as
measured by the control.
Conditions:
Application Mode is set to PWM,
Boil or Elec and a snow/ice sensor or slab
sensor is installed.
DRY or WET
User
Installer
WATER SENSOR
— Current status of the
water detection sensor.
Conditions:
A snow/ice sensor or snow
sensor is installed.
– – –,
70 to 200ºF
(21.0 to 93.5ºC)
Installer
BOILER TARGET
— This field displays
the calculated boiler target of the snow
melt system. Three dashes (– – –) display
when the snow melt control is not operating
the boiler.
Conditions:
Application Mode is set to Boil.
-58 to 212ºF
(50.0 to
100.5ºC)
Installer
SUPPLY
— Shows the current system supply
temperature as measured by the control.
Conditions:
Application Mode is set to PWM
or Boil.