78
WARNING:
In the event that any of the parts are replaced, refer to the relevant section of the
instruction manual and fulfill the requirements prior to operating the device again.
13.5. After Two Weeks of Study
The following checks should be carried out following the two-week operation without any problems:
Operative currents of the compressor and fan motors
Operation temperature of the compressor and fan motors
Status of the filters
Carry out condensation and drainage in order to see the water flow in the pan
Operation Status of the control systems
Sound levels should be checked in the Operation Status of the device equipment.
The device main electricity supply voltage values should be checked.
13.6. Cleaning the Device
Read carefully, and make sure that you understand, the following instructions prior to starting to clean the
device. It should never be ignored that improper and incorrect applications may cause damage to the device
and the operator during all the cleaning operations.
Fulfill the following instructions prior to dismantling the device or starting the cleaning operations as all the
devices have moving and pressured parts.
Make sure that all the electricity connections have been cut off. Not only lifting the power switch, all the
electricity connections should be removed from their mount Clemens, and a warning of maintenance
should be posted on the panel.
Make sure that all the moving parts have stopped completely.
All the switches on the supply line should be taken to the on (no electricity) position.
These instructions apply only to the cleaning of Attic Type air conditioners. It is supposed that all the other
parts of the system (inner parts of air channels, culverts and shades opening outdoors, culvers of air turning
from the room, damping supply water cleaning, condensation water drainage systems etc…) have been
cleaned in compliance with the instructions provided by their manufacturers.
It should never taken to mean that fulfilling the cleaning and disinfection operations according to these
instructions will insure the wanted hygienic conditions of the place. Air conditioning systems cannot make
the environment hygienic. They are used only to maintain the hygienic conditions currently in place. The
user will be responsible for monitoring, and replacing on time, HEPA filters on the exit of the system.