TSB-KK-008 rev.00
1. INTRODUCTION AND GENERAL NOTIFICATIONS
The manual hereby was prepared according to TS 11823/95 Standard and users need to know these
instructions and the other montage instructions given with this manual before starting-up their
devices. With this manual, a high-security reference guide was envisioned to be prepared for
installation, commissioning, operation and maintenance of roof type devices (URTP). The users must
refer to the information in this manual with high importance for their own safety and comfort.
1.1. General Warnings
Pay attention to the transport and conservation conditions in the instruction manual.
Absolutely comply with EN378 or ISO5149 standards for installation.
After having received and before commissioning the device, certainly perform a damage control. Be sure that
cooling circuits aren’t undamaged and they haven’t and damage to cause leakages. In case any damage is
detected, absolutely contact the relevant departments.
List of spare parts should be requested from the company for use when required.
Temperature values should be between -25 and +55 Celsius at conservation area.
Devices are for outer areas and were designed to operate at a clean environment. Conserving devices at risky
environments for short or long periods may lead to temporary or permanent damages in them: Severely humid
environments (humid basements, near sea, lake and river etc.), environments where a part of the devices may
soak into water and where they may be covered with excessive dust or be earthen up, environments near areas
such as boiler flue kitchen flue, car park flue, cesspool or sewage flue, placements on inclined area more than
15º, under rainwater gutters, under trees where there may sometimes be leakage such as pine and palm trees,
near walls where work is being carried on.
This unit designed for the outdoor conditions, not for use indoor conditions. The unit should be placed
somewhere obstructing access by impotent people, moreover this position should absolutely be away from
ignitable, explosives and inflammables.
Packaging shouldn’t be removed until the device reaches to the installation point so that no damage occurs on
the device.
Personnel to work on these units should be trained and licensed (licensed according to BA4 if IEC 60364
categorization).
In devices with hot water coil, water within the heat exchanger should be drained through drainage valve on
the equipments when water heat exchanger isn’t used and the outer temperature drops under 3ºC.
In devices with hot water coil, plastic plugs shouldn’t be taken away from heat exchanger pipe outlets until
pie connections are ready.
In devices with hot water coil, hot water circulation should be going on even if the device stops at days when
the outer temperature drops under 3ºC.
In devices with hot water coil, water temperature flowing to the heat exchanger shouldn’t be lower than +35
ºC.
Heat exchangers should be controlled against the possibility of having been damaged during transportation, if
required, aluminum lamellas should be corrected by combing (if they have been smashed).