40
7.2. Gas Connection
Gas connection of the device’s gas firing unit should be provided suitably to the gas pass equipments
described below and in the right alignment.
IMPORTANT:
Gas connections should be made with gas pipes in compliance with local rules. Tightening
torque values for gas pipes are as follows.
-Ø ¾”: 150Nm. / -Ø 1”: 200Nm. / -Ø 1 1/2”: 300Nm.
Standard equipments within the device;
①
Main burning gas solenoid valve
②
Pilot light gas solenoid valve
③
Pressure compensating regulator
④
Safety gag solenoid valve
⑤
Small gas filter
Equipments to be adjusted to the device’s gas
pass;
⑥
Vibration isolator connection
⑦
Gas filter
⑧
Gas valve