Technopel Compact Pellet Boiler Installation and User’s Manual
The fuels that burn in the boiler should be kept at a distance of at least 80 cm away from the boiler. It
is recommended to store in a different room.
DANGEROUS
It is dangerous to store flammable and easily ignitable materials in the boiler room.
Dimensions of Installation Places
Boilers should be installed on a concrete base at a height of 10 cm from the ground to protect water
from moisture and fuel from ash dust. The concrete base avoids the fume extractor’s suction of ash
dust and fuel on the floor. Laying tiles makes cleaning easier.
The boiler room should be sized to ensure minimum dimensions around the boiler as shown in the
figure below. It is necessary to consider the distance to add the bunker when the boiler is placed. The
burner under the bunker should be easily removed and able to work comfortably.
A: At least 80 cm is required for comfortable use of the cleaning arm and technical service actions;
B: At least 100 cm is required for assembly and disassembly of the burner equipment;
C: At least 80 cm is required for chimney connection and technical service actions;
D: The dimensions of the boiler type should be taken into account so that the front cover can be
easily opened and used.
If the above dimensions are followed, the legal requirement for a minimum 8 m
3
volume is met.
A (cm)
B (cm)
C (cm)
D (cm)
Technopel 15
100
70
50
40
Technopel 24
100
70
50
40
Technopel 36
100
70
50
40
Technopel 48
100
70
50
40