Technopel, Pelet Yakıtlı Sıcak Su Kazanı İşletme ve Bakım Kılavuzu
Press the ENTER button
and use the arrow buttons
to set the desired boiler
temperature. After entering the desired value with the arrow buttons, press the ENTER
button
again and save the value. The boiler will start to work and pre-purge will be done during the set time.
Follow these stages Start-up, Ignition 1, Ignition 2 modes, respectively.
Ignition may not start in initial operation after these modes completed. In the first stage, the ignition
may not able to start due to an empty fuel feeding channel. Please press ESC button
for 5
seconds when you see an error message to reset it. Boiler pass to Power 3 after ignition stages and
follow Power 4,5 and 6 mode, respectively. The boiler continues to work until reaches to set
temperature value.
It decreases and increases the excess power when it approaches the set temperature value. When it
reaches the set temperature, Power 0 (Standby Mode) will start when it reaches the set value.
It is possible to select manual or automatic operation of the boiler by first press the MOD
button and then select the arrow button
. If you select automatic operation, it goes starting
from Power 3 to Power 6, respectively. Power drops down until Power 0 when it reachs to the set
temperature value.
Power 6
Power 5
Power 4
Power 3
Power 2
Power 1
100%
80%
60%
50%
40%
30%
The power mode can be selected according to requested value for the boiler power effective use
percentage, when you want to operate manually.
MAINTENANCE & CLEANING PROCESS
DANGEROUS
Regular maintenance is required
by the authorized technical
service for effective use of the
boiler.
Regular Controls:
• Please always check water level. Water pressure of the manometer should be marked after first
filling. the pressure rises when the water warms. For this reason, the marked water pressure level on
the manometer should be checked when the water is cold. If the water pressure is below the static
pressure or lower than the system setting, water must be added to the system while the boiler is
cold. In order to protect the system and the boiler from corrosion, the feeding water should be
softened according to the local settings. Please consider the below items during regular controls:
• Please check the front door is closed properly and replace the cover gaskets if necessary.
• Ensure that there is no gas leakage in the flue connection, if there is, it should be solved
immediately.
• Please check the fan work properly. A periodically balanced fan may run noisy.