Control connection
DS 400-2
04/2019 - V01
36
Dig
ital in
pu
t
5
Control connection
5.1
Digital input
6 Opto-input
DS-BAx-DPC/E-DS-400-digi-in-2
Input voltage
H-level (On)
+10 bis +30 V
L-level (Off)
<+6 V
Input current
Max. 7,5 mA
Ratet voltage / cure
24 V/6 mA
Reference ground
GNDE (X1:10)
The enable input (FRG/RUN) and the input for the rotating field enable (RFE) are fixed, they
cannot be programmed.
Without the enable FRG/RUN the servo-drive is electronically disabled (no PWM pulses).
Without the rotating field enable RFE the rotating field of the output stage is additionally
electronically disabled (2
nd
disable channel). The drive is free of torque (no holding torque).
The remaining four digital inputs can be programmed.
The inputs LMT1 (X1:5) and LMT2 (X1:6) are preferably to be used as inputs of the output stage
switch.
Input
Connection Function
State
FRG/RUN
X1:7
Enable
fixed
RFE
X1:18
Rotating field enable
fixed
END1/LMT1
X1:5
Output stage switch 1/Digital
input
programmable
END2/LMT2
X1:6
Output stage switch 2/Digital
input
programmable
DIN1
X1:11
Digital input 1
programmable
DIN2
X1:12
Digital input 2
programmable
External voltage supply for the inputs and outputs
DS-BAx-DPC/E-DS-400-Logi
X1:5
END1/LMT1
X1:6
END2/LMT2
X1:7
FRG/RUN
X1:11
DIN1
X1:12
DIN2
VCC
PAx
3k9
1k5
100nF
100nF
Digital
10...30V=
Input
DSxx/BAxx
X1:18
RFE
Digital input
Limit switch 1
Limit switch 2
Enable
Digital Input 1
Digital Input 2
Rotation-enable
(X1:E)
(X1:F)
(X1:G)
(X1:L)
(X1:M)
(X1:T)
(IP65)
+24V for the logic and the auxiliary
voltage
GNDE logic ground